ECC800 Data Center Controller
User Manual (for ECC800-Pro)
6.7.1 Connecting a Communications Cable
Procedure
Step 1 Connect the T/H sensor to the COM1 port on the ECC800-Pro using a network
cable.
Step 2 Connect the infrared remote control module to the T/H sensor using a network
cable.
----End
6.7.2 Setting and Adding an Infrared Remote Control Module
Prerequisites
●
●
●
Context
After an infrared remote control module is replaced, you need to add the new
infrared remote control module on the ECC800-Pro WebUI.
Procedure
Step 1 Set monitoring parameters for the infrared remote control module.
1.
Table 6-39 Setting a device address
Address
1
2
Issue 02 (2020-09-07)
The infrared remote control module is connected to the ECC800-Pro, and both
are powered on.
You have obtained the IP address of the ECC800-Pro as well as the user name
and password used for WebUI login.
You have prepared a PC with an IP address in the same network segment as
that of the ECC800-Pro, and the PC is connected to the WAN port on the
ECC800-Pro.
Set the device address to 2 by setting the DIP switch on the infrared remote
control module.
Table 6-39
The DIP switch consists of toggle switches 1–5 (from left to right). Toggle
switches 1–4 specify the address of the infrared remote control module.
Toggle switch 5 specifies the address of the RS485 build-out resistor. 0
indicates OFF and 1 indicates ON. Toggle switch 5 is set to OFF.
Toggle
Switch 1
ON
OFF
Copyright © Huawei Technologies Co., Ltd.
describes how to set the DIP switch.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
6 Feature Description
Toggle
Switch 4
OFF
OFF
203