APPENDICES
(2) Parameter setting
To connect FR-A700 series, set the following in the system setting of
MT Developer2.
(a) When using Q173DSCPU/Q172DSCPU
• Set " SSCNET " for communication type in SSCNET setting.
• Set the amplifier model in amplifier setting to "FR-A700".
(b) When using Q173DCPU(-S1)/ Q172DCPU(-S1)
• Set the amplifier model in amplifier setting to "FR-A700".
(3) Control of FR-A700 series parameters
Parameters set in FR-A700 series are not controlled by Motion CPU.
Set the parameters by connecting FR-A700 series directly with the operation
panel on the front of inverter (FR-DU07/FR-PU07) or FR Configurator that is
inverter setup software. For details on setting items for FR-A700 series, refer to
the instruction manual of the FR-A700 series.
POINT
In the state of connecting between FR-A700 series and Motion CPU, only a part of
parameters can be set if the parameter of the inverter " Pr.77 Parameter write
selection" is in the initial state. Set "2: Write parameters during operation" to rewrite
the parameters of FR-A700 series.
APP - 97