1MRS759142 C
11.2.1.4
REX640
Technical Manual
UK rectifier inverse-time characteristic
The UK rectifier type simulates the rectifier bridge.
The operate times are defined with the coefficients A, B and C.
The values of the coefficients can be calculated according to the formula
A
t s
[ ] =
B k
+
⋅
c
I
1
−
I
>
GUID-B27F8BAE-0F5F-4151-922C-D08B6261B1D7 V1 EN
t[s] Operate time in seconds
I
Measured current
Start value
I>
Set
Time multiplier
k
Set
Table 1473:
Curve parameters for UK rectifier
Operating curve type
A
(20) UK rectifier
45900
General function block features
B
0
Section 11
(Equation 358)
C
5.6
1679