Commissioning A Temperature Sensor (Connected To The Ntc Port On The Rack Environment Unit); Commissioning A T/H Sensor; Commissioning A T/H Sensor (Bom Number:33010346) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
1.
2.
3.
4.
5.
Step 2 Check the monitoring functions of temperature sensor.
Table 5-31 Commissioning the sensor
Check Method
View the operating information
about the temperature sensor on
the WebUI.
----End
5.7.4.2 Commissioning a Temperature Sensor (Connected to the NTC port
on the rack environment unit)
If a temperature sensor is installed, perform the following steps to configure it.
Procedure
Step 1 The temperature sensor supports self-discovery and does not need to set parameters.
Step 2 Check the monitoring functions of temperature sensor.
Table 5-32 Commissioning the sensor
Check Method
Path: Monitoring > Cabinet >
IT Cabinet n > Cabinet
Collector n
----End

5.7.5 Commissioning a T/H Sensor

5.7.5.1 Commissioning a T/H Sensor (BOM number:33010346)

If a T/H sensor is installed, perform the following steps to configure it.
Issue 02 (2019-02-28)
In this example, the temperature sensor is connected to the AI/DI_2 port on the ECC800.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_2 Port
Settings.
Set AI/DI_2 sensor to Enable, and click Submit.
Set AI/DI_2 sensor name to Temperature sensor.
Check that AI/DI_2 sensor type is set to NTC. Ensure that AI/DI_2 power supply is
Yes, and click Submit.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
You can view the current cabinet temperature.
Normal Connection Status
You can view the current cabinet temperature.
5 Power-On Commissioning
132