ECC800 Data Center Controller
User Manual
Item
Power input
Power output
FE port
PoE port
BLINK
button
Indicators
Table 3-20 Indicators on a smart ETH gateway
Indicator
PWR
RUN
Issue 02 (2019-02-28)
Specifications
PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
48V_OUT1 and 48V_OUT2, terminal, output voltage range: 45–55 V
DC
Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upper computer
Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3at
If you press the BLINK button, the RUN indicator blinks intermittently at
super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 10 seconds.
Color
Name
Green
Power input
status indicator
Green
Module
running status
indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power supply is
abnormal.
Blinking at
The smart ETH gateway
long
successfully registers with
intervals
the ECC800 and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at
The smart ETH gateway does
short
not register with the ECC800
intervals
(the indicator blinks at 4 Hz,
on for 0.125s and then off for
0.125s).
Blinking
The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.