ECC800 Data Center Controller
User Manual
Table 5-26 Commissioning the sensor
Check Method
Simulate a smoky
environment under
the smoke sensor.
----End

5.7.3 Commissioning a Water Sensor

5.7.3.1 Commissioning a WLDS900 water sensor

If a water sensor is installed, perform the following steps to configure it.
Procedure
Step 1 Set water sensor parameters.
1.
2.
3.
4.
5.
Step 2 Check functions of water sensors.
Table 5-27 Function commissioning
Check Method
Immerse the water detection
cable in water.
----End

5.7.3.2 Commissioning a WLDS600 Water Sensor

Procedure
Step 1 The default communications address 1 of the water sensor is used for connecting to the
ECC800.
Issue 02 (2019-02-28)
Normal Connection Status
DI1_smoke alarm is displayed
on the active alarm page of the
app or WebUI.
In this example, the water sensor is connected to the AI/DI_4 port on the ECC800.
The default alarm severity of the AI/DI port is Minor. If you want to change the alarm severity, see
9.1.7 How to Set Parameters for Alarm Enable, Severity, and Loudspeaker?.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_4 Port
Settings.
Set AI/DI_4 sensor to Enable, and click Submit.
Set AI/DI_4 sensor name to Leak sensor.
Check that AI/DI_4 sensor type is Leak sensor(Rope). Ensure that AI/DI_4 power
supply is Yes, and click Submit.
Copyright © Huawei Technologies Co., Ltd.
Alarm Clearance Method
Press the reset button of the
smoke sensor to clear the alarm.
Normal Connection Status
Leak sensor AI/DI_4 DI alarm is generated on the
active alarm screen of the app or on the WebUI.
5 Power-On Commissioning