ECC800 Data Center Controller
User Manual
Item
FE port
PoE port
BLINK button
Table 3-22 Indicators on the general input unit
Indicator
PWR
RUN
ALM
Issue 02 (2019-02-28)
Specifications
Two FE ports, RJ45 terminal with an indicator, 10/100M
communications rate, for cascading between the general input unit
and the power distribution unit and for communication with the
upstream device.
Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, 45–55 V DC power output.
If you press the BLINK button, the RUN indicator blinks
intermittently at super short intervals (blinking at super short
intervals for 0.5s and then off for 0.5s) for 10s.
Color
Name
Green
Power input
status indicator
Green
Module running
status indicator
Red
Alarm indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is
normal.
Off
There is no power
input.
Off
The power input is
abnormal.
Blinking at long
The general input unit
intervals
has successfully
registered with the
ECC800 and the
software runs properly
(blinking at 0.5 Hz, on
for 1s and then off for
1s).
Blinking at short
The general input unit
intervals
has failed to register
with the ECC800
(blinking at 4 Hz, on
for 0.125s and then off
for 0.125s).
Blinking
The indicator blinks at
super short intervals
(blinking at 10 Hz, on
for 0.05s and then off
for 0.05s) for 0.5s, and
then turns off for 0.5s.
The cycle lasts for
10s.
Steady on
A system failure alarm
is generated.
3 Device Description
27