Commissioning The Exit Button, Emergency Button, And Magnetic Lock - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Table 5-41 Function check
Check Method
Method 1: Attempt to open the door using
the configured authentication mode.
Method 2: On the WebUI, choose
Monitoring > Aisle > Access Actuator
Group > Access Actuator n, and click
Controls to open the door remotely.
Step 5 Check the functions of the cabinet electric lock.
Table 5-42 Function check
Check Method
Method 1: Ensure that the cabinet door is
closed, and attempt to open the door with an
IC card.
Method 2: On the WebUI, choose
Monitoring > IT Cabinet > IT Cabinet
n > E-LOCK n, and click Controls to open
the door remotely.
----End
5.7.8 Commissioning the Exit Button, Emergency Button, and
Magnetic Lock
Procedure
Step 1 Check functions of the exit button.
Table 5-43 Function commissioning
Check Method
Attempt to open the door by pressing the
exit button when the aisle door is closed.
Step 2 Check functions of the emergency button.
Table 5-44 Function commissioning
Check Method
Issue 02 (2019-02-28)
Normal Connection
Status
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Normal Connection Status
For method 1: The aisle door is opened
successfully.
For method 2: After you choose Query >
Access Event on the WebUI, you can view
the type of this access control event.
Normal Connection Status
For method 1: Swipe an authorized IC card,
press the lower part of the cabinet electronic
lock when the green indicator blinks, and
open the cabinet electronic lock.
For method 2: After you choose Query >
Access Event on the WebUI, you can view
the type of this access control event.
Normal Connection Status
The aisle door is opened successfully.
Follow-up Procedure