Huawei ECC800 User Manual page 38

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Item
FE port
PoE port
BLINK button
Table 3-24 Indicators on the power distribution unit
Indicator
PWR
RUN
ALM
Issue 02 (2019-02-28)
Specifications
Two FE ports, RJ45 terminal with an indicator, 10/100M
communications rate, for cascading between power distribution
units and between the power distribution unit and general input unit
Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, 45–55 V DC power output
If you press the BLINK button, the RUN indicator blinks
intermittently at super short intervals (blinking at super short
intervals for 0.5s and then off for 0.5s) for 10s.
Color
Name
Green
Power input
status indicator
Green
Module
running status
indicator
Red
Alarm
indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power input is
abnormal.
Blinking at long
The power distribution unit
intervals
has successfully registered
with the ECC800 and the
software runs properly (the
indicator blinks at 0.5 Hz,
on for 1s and then off for
1s).
Blinking at
The power distribution unit
short intervals
has failed to register with
the ECC800 (the indicator
blinking at 4 Hz, on for
0.125s and then off for
0.125s).
Blinking
The indicator blinks at super
short intervals (blinking at
10 Hz, on for 0.05s and then
off for 0.05s) for 0.5s, and
then turns off for 0.5s. The
cycle lasts for 10s.
Steady on
A system failure alarm is
generated.
Off
No system alarm is
generated.
3 Device Description
29