Connecting The Control Cables; I/O Terminals - ABB ACS355 User Manual

Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

Connecting the control cables

I/O terminals

The figure below shows the I/O terminals. Tightening torque is 0.4 N·m / 3.5 lbf·in.
1 2 3 4 5 6 7 8 17 18 19
S1
mA
V
9 10 11 12 13 14 15 16 20 21 22
X1A
Voltage and current selection for analog inputs
Switch S1 selects voltage (0 [2]...10 V / -10...10 V) or current (0 [4]...20 mA /
-20...20 mA) as the signal types for analog inputs AI1 and AI2. The factory settings
are unipolar voltage for AI1 (0 [2]...10 V) and unipolar current for AI2 (0 [4]...20 mA),
which correspond to the default usage in the application macros. The switch is
located to the left of I/O terminal 9 (see the I/O terminal figure above).
ON
Top position (ON): I (0 [4]...20 mA, default for AI2; or -20...20 mA)
S1
Bottom position (OFF): U (0 [2]...10 V, default for AI1; or -10...10 V)
1
2
X1C:STO
1 2 3 4
X1B
Electrical installation 51
X1A:
X1B:
1: SCR
17: ROCOM
2: AI1
18: RONC
3: GND
19: RONO
4: +10 V
20: DOSRC
5: AI2
21: DOOUT
6: GND
22: DOGND
7: AO
X1C:STO
8: GND
9: +24 V
1: OUT1
10: GND
2: OUT2
11: DCOM
3: IN1
12: DI1
4: IN2
13: DI2
14: DI3
15: DI4
16: DI5 digital or frequency input
S1: Selects voltage or current as
the signal types for analog
inputs AI1 and AI2.