Fault tracing
What this chapter contains
The chapter tells how to reset faults and view fault history. It also lists all alarm and
fault messages including the possible cause and corrective actions.
Safety
WARNING! Only qualified electricians are allowed to maintain the drive. Read
the safety instructions in chapter
drive.
Alarm and fault indications
Fault is indicated with a red LED. See section
An alarm or fault message on the panel display indicates abnormal drive status.
Using the information given in this chapter, most alarm and fault causes can be
identified and corrected. If not, contact an ABB representative.
The four digit code number in parenthesis after the fault is for the fieldbus
communication. See chapters
and
Fieldbus control with fieldbus adapter
How to reset
The drive can be reset either by pressing the keypad key
RESET
(assistant control panel), through digital input or fieldbus, or by switching the
supply voltage off for a while. The source for the fault reset signal is selected by
Safety
on page
LEDs
Fieldbus control with embedded fieldbus
on page 325.
Fault tracing 335
17
before you work on the
on page 356.
RESET
EXIT
(basic control panel) or
on page