Reference Types And Processing; Settings; Diagnostics - ABB ACS355 User Manual

Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

128 Program features

Reference types and processing

The drive can accept a variety of references in addition to the conventional analog
input and control panel signals.
• The drive reference can be given with two digital inputs: One digital input
increases the speed, the other decreases it.
• The drive can form a reference out of two analog input signals by using
mathematical functions: addition, subtraction, multiplication and division.
• The drive can form a reference out of an analog input signal and a signal received
through a serial communication interface by using mathematical functions:
addition and multiplication.
• The drive reference can be given with frequency input.
• In external control location EXT1/2, the drive can form a reference out of an
analog input signal and a signal received through Sequence programming by
using a mathematical function: addition.
It is possible to scale the external reference so that the signal minimum and
maximum values correspond to a speed other than the minimum and maximum
speed limits.

Settings

Parameter
Group
11 REFERENCE SELECT
Group
20 LIMITS
Group
22 ACCEL/DECEL
Group
24 TORQUE CONTROL
Group
32 SUPERVISION

Diagnostics

Actual signal
0111/0112
Group
03 FB ACTUAL SIGNALS
Additional information
External reference source, type and scaling
Operating limits
Speed reference acceleration/deceleration ramps
Torque reference ramp times
Reference supervision
Additional information
REF1/REF2 reference
References in different stages of the reference
processing chain