322 Fieldbus control with embedded fieldbus
DCU profile Control word, parameter
Bit
Name
28
REF_AVE
29
LINK_ON
30
REQ_STARTINH 1
31
Reserved
Status words
The following tables describe the Status word content for the DCU profile.
Bit
Name
0
READY
1
ENABLED
2
STARTED
3
RUNNING
4
ZERO_SPEED
5
ACCELERATE
6
DECELERATE
7
AT_SETPOINT
8
LIMIT
9
SUPERVISION
10
REV_REF
11
REV_ACT
Value
Information
1
Average speed reference request.
This is an internal control bit. Only for supervision.
0
No operation
1
Master detected on fieldbus link.
This is an internal control bit. Only for supervision.
0
Fieldbus link is down.
Start inhibit
0
No start inhibit
DCU profile Status word, parameter
Value
Status
1
Drive is ready to receive start command.
0
Drive is not ready.
1
External Run enable signal received.
0
No external Run enable signal received.
1
Drive has received start command.
0
Drive has not received start command.
1
Drive is modulating.
0
Drive is not modulating.
1
Drive is at zero speed.
0
Drive has not reached zero speed.
1
Drive is accelerating.
0
Drive is not accelerating.
1
Drive is decelerating.
0
Drive is not decelerating.
1
Drive is at setpoint. Actual value equals reference
value (ie is within tolerance limits).
0
Drive has not reached setpoint.
1
Operation is limited by group
0
Operation is within group
1
A supervised parameter (group
outside its limits.
0
All supervised parameters are within limits.
1
Drive reference is in reverse direction.
0
Drive reference is in forward direction.
1
Drive is running in reverse direction.
0
Drive is running in forward direction.