Power Cable Sizes And Fuses - ABB ACS355 User Manual

Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

Power cable sizes and fuses

Cable dimensioning for rated currents (I
the corresponding fuse types for short-circuit protection of the input power cable. The
rated fuse currents given in the table are the maximums for the mentioned fuse
types. If smaller fuse ratings are used, check that the fuse rms current rating is larger
than the rated I
current given in section
1N
is needed, multiply current I
page 38.
Check that the operating time of the fuse is below 0.5 seconds. The operating
time depends on the fuse type, the supply network impedance as well as the cross-
sectional area, material and length of the supply cable. In case the 0.5 seconds
operating time is exceeded with the gG or T fuses, ultra rapid (aR) fuses will in most
cases reduce the operating time to an acceptable level.
Note: Larger fuses must not be used when the input power cable is selected
according to this table.
Type
ACS355-
gG
x = E/U
A
1-phase U
= 200...240 V (200, 208, 220, 230, 240 V)
N
01x-02A4-2
10
01x-04A7-2
16
01x-06A7-2
16/20
01x-07A5-2
20/25
01x-09A8-2
25/35
3-phase U
= 200...240 V (200, 208, 220, 230, 240 V)
N
03x-02A4-2
10
03x-03A5-2
10
03x-04A7-2
10
03x-06A7-2
16
03x-07A5-2
16
03x-09A8-2
16
03x-13A3-2
25
03x-17A6-2
25
03x-24A4- 2
63
03x-31A0-2
80
03x-46A2-2
100
by 1.5. See also section
1N
Fuses
UL Class
Supply
T (600 V)
(U1, V1, W1)
2
A
mm
10
2.5
20
2.5
1)
25
2.5
1)
30
2.5
1)
35
6
10
2.5
10
2.5
15
2.5
15
2.5
15
2.5
20
2.5
30
6
35
6
60
10
80
16
100
25
) is shown in the table below together with
1N
Ratings
on page 358. If 150% output power
Selecting the power cables
Size of copper conductor in cablings
Motor
(U2, V2, W2)
2
AWG mm
AWG mm
14
0.75
18
14
0.75
18
10
1.5
14
10
1.5
14
10
2.5
12
14
0.75
18
14
0.75
18
14
0.75
18
12
1.5
14
12
1.5
14
12
2.5
12
10
6
10
10
6
10
8
10
8
6
16
6
2
25
2
Technical data 361
PE
Brake
(BRK+, BRK-)
2
2
AWG
mm
2.5
14
2.5
2.5
14
2.5
2.5
10
2.5
2.5
10
2.5
6
10
6
2.5
14
2.5
2.5
14
2.5
2.5
14
2.5
2.5
12
2.5
2.5
12
2.5
2.5
12
2.5
6
10
2.5
6
10
2.5
10
8
6
16
6
10
16
4
10
on
AWG
14
14
12
12
12
14
14
14
12
12
12
12
12
10
8
8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents