ABB ACS355 User Manual page 243

Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

All parameters
No.
Name/Value
3010 STALL
FUNCTION
NOT SEL
FAULT
ALARM
3011 STALL
FREQUENCY
0.5...50.0 Hz
3012 STALL TIME
10...400 s
3013 UNDERLOAD
FUNC
NOT SEL
Description
Selects how the drive reacts to a motor stall condition. The
protection wakes up if the drive has operated in a stall
region (see the figure below) longer than the time set by
parameter
3012 STALL
In vector control the user defined limit =
TORQUE 1
/
2018 MAX TORQUE 2
and negative torques).
In scalar control the user defined limit =
CURRENT.
The control mode is selected by parameter
CTRL
MODE.
·
0.95
User defined limit
Protection is inactive.
The drive trips on fault
motor coasts to stop.
The drive generates alarm
Defines the frequency limit for the stall function. See
parameter
3010 STALL
Frequency
Defines the time for the stall function. See parameter
STALL
FUNCTION.
Time
Selects how the drive reacts to underload. The protection
wakes up if:
• the motor torque falls below the curve selected by
parameter
3015 UNDERLOAD
• output frequency is higher than 10% of the nominal motor
frequency and
• the above conditions have been valid longer than the time
set by parameter
3014 UNDERLOAD
Protection is inactive.
Actual signals and parameters 243
TIME.
2017 MAX
(applies for positive
2003 MAX
Torque (%) /
Current (A)
Stall region
MOTOR STALL
(0012) and the
MOTOR STALL
FUNCTION.
CURVE,
TIME.
Def/FbEq
NOT SEL
9904 MOTOR
f
Par.
3011
0
1
(2012).
2
20.0 Hz
1 = 0.1 Hz
3010
20 s
1 = 1 s
NOT SEL
0