310 Fieldbus control with embedded fieldbus
Fieldbus reference scaling
Fieldbus references REF1 and REF2 are scaled for the ABB drives profile as shown
in the following table.
Note: Any correction of the reference (see section
correction
on page 310) is applied before scaling.
Reference Range
REF1
-32767
...
+32767
REF2
-32767
...
+32767
Note: The settings of parameters
effect on the reference scaling.
Reference
Scaling
type
Speed or
-20000 = -(par. 1105)
frequency
0 = 0
+20000 = (par. 1105)
(20000 corresponds to 100%)
Speed or
-10000 = -(par. 1108)
frequency
0 = 0
+10000 = (par. 1108)
(10000 corresponds to 100%)
Torque
-10000 = -(par. 1108)
0 = 0
+10000 = (par. 1108)
(10000 corresponds to 100%)
PID
-10000 = -(par. 1108)
reference
0 = 0
+10000 = (par. 1108)
(10000 corresponds to 100%)
1104 REF1 MIN
Reference selection and
Remarks
Final reference limited by
1104/1105. Actual motor
speed limited by
(speed) or
(frequency).
Final reference limited by
1107/1108. Actual motor
speed limited by
(speed) or
(frequency).
Final reference limited by
2015/2017
2016/2018
Final reference limited by
4012/4013
4112/4113
and
1107 REF2 MIN
2001/2002
2007/2008
2001/2002
2007/2008
(torque 1) or
(torque 2).
(PID set 1) or
(PID set 2).
have no