All parameters
No.
Name/Value
0 = NOT SEL
0...10000 ms
4306 RUNTIME
FREQ LVL
0.0 = NOT SEL
0.0...100.0%
4307 BRK OPEN
LVL SEL
PAR 4302
MEMORY

50 ENCODER

5001 PULSE NR
32...16384 ppr Pulse number in pulses per round (ppr)
5002 ENCODER
ENABLE
DISABLE
ENABLE
5003 ENCODER
FAULT
FAULT
ALARM
5010 Z PLS ENABLE Enables the encoder zero (Z) pulse. Zero pulse is used for
DISABLE
ENABLE
5011 POSITION
RESET
DISABLE
ENABLE
Description
magnetizing time. If parameter value is set to zero, the
function is disabled.
Defines the brake close speed. When frequency falls below
the set level during run, the brake is closed. The brake is re-
opened when the requirements set by parameters
4301...4305
are met.
Value in percent of the maximum frequency (in scalar
control) or the maximum speed (in vector control). If
parameter value is set to zero, the function is disabled. The
control mode is selected by parameter
MODE.
Selects the torque (in vector control) or current (in scalar
control) applied at brake release.
Value of parameter
4302 BRAKE OPEN LVL
Torque value (in vector control) or current value (in scalar
control) saved in parameter
used.
Useful in applications where initial torque is needed to
prevent unintended movement when the mechanical brake
is released.
Encoder connection.
For more information, see MTAC-01 pulse encoder interface
module user's manual (3AFE68591091 [English]).
States the number of encoder pulses per one revolution.
Enables the encoder.
Disabled
Enabled
Defines the operation of the drive if a failure is detected in
communication between the pulse encoder and the pulse
encoder interface module, or between the module and the
drive.
The drive trips on fault
The drive generates alarm
position reset.
Disabled
Enabled
Enables the position reset.
Disabled
Enabled
Actual signals and parameters 275
9904 MOTOR CTRL
0179 BRAKE TORQUE MEM
ENCODER ERR
(0023).
ENCODER ERROR
Def/FbEq
1 = 1 ms
0.0 =
NOT SEL
1 = 0.1%
PAR 4302
used.
1
2
1024 ppr
1 = 1 ppr
DISABLE
0
1
FAULT
1
(2024).
2
DISABLE
0
1
DISABLE
0
1