All parameters
No.
Name/Value
2621 SMOOTH
START
NO
YES
2622 SMOOTH
START CUR
10...100%
2623 SMOOTH
START FRQ
2...100%
29 MAINTENANCE
TRIG
2901 COOLING FAN
TRIG
0.0...6553.5 kh Time. If parameter value is set to zero, the trigger is
2902 COOLING FAN
ACT
0.0...6553.5 kh Time. Parameter is reset by setting it to zero.
2903 REVOLUTION
TRIG
0...65535 Mrev Millions of revolutions. If parameter value is set to zero, the
Description
Selects the forced current vector rotation mode at low
speeds. When the smooth start mode is selected, the rate of
acceleration is limited by the acceleration and deceleration
ramp times (parameters
driven by the permanent magnet motor has high inertia,
slow ramp times are recommended.
Can be used for permanent magnet motors only.
Disabled
Enabled
Current used in the current vector rotation at low speeds.
Increase the smooth start current if the application requires
high pull-up torque. Decrease the smooth start current if
motor shaft swinging needs to be minimized. Note that
accurate torque control is not possible in the current vector
rotation mode.
Can be used for permanent magnet motors only.
Value in percent of the motor nominal current
Output frequency up to which the current vector rotation is
used.
Can be used for permanent magnet motors only.
Value in percent of the motor nominal frequency
Maintenance triggers
Defines the trigger point for the drive cooling fan run time
counter. Value is compared to parameter
FAN ACT
value.
disabled.
Defines the actual value for the cooling fan run time counter.
When parameter
2901 COOLING FAN TRIG
to a non zero value, the counter starts. When the actual
value of the counter exceeds the value defined by
parameter 2901, a maintenance notice is displayed on the
panel.
Defines the trigger point for the motor revolution counter.
Value is compared to parameter
value.
trigger is disabled.
Actual signals and parameters 237
2202
and 2203). If the process
2902 COOLING
2904 REVOLUTION ACT
Def/FbEq
NO
0
1
50%
1 = 1%
10%
1 = 1%
0.0 kh
1 = 0.1 kh
0.0 kh
has been set
1 = 0.1 kh
0 Mrev
1 =
1 Mrev