270 Actual signals and parameters
All parameters
No.
Name/Value
4025 WAKE-UP DEV Defines the wake-up deviation for the sleep function. The
x...x
4026 WAKE-UP
DELAY
0.00...60.00 s
4027 PID 1 PARAM
SET
SET 1
DI1
DI2
DI3
DI4
DI5
SET 2
TIMED FUNC 1 Timed PID SET 1/2 control. Timed function 1 inactive = PID
TIMED FUNC 2 See selection
TIMED FUNC 3 See selection
TIMED FUNC 4 See selection
DI1(INV)
Description
drive wakes up if the process actual value deviation from
the PID reference value exceeds the set wake-up deviation
(4025) longer than the wake-up delay (4026). Wake-up level
depends on parameter
If parameter
4005
is set to 0:
Wake-up level = PID reference (4010) - Wake-up deviation
(4025).
If parameter
4005
is set to 1:
Wake-up level = PID reference (4010) + Wake-up deviation
(4025)
PID reference
See also figures for parameter
Unit and range depend on the unit and scale defined by
parameters
4026 WAKE-UP DELAY
SCALE.
Defines the wake-up delay for the sleep function. See
parameter
4023 PID SLEEP
Wake-up delay
Defines the source from which the drive reads the signal
that selects between PID parameter set 1 and 2.
PID parameter set 1 is defined by parameters 4001...4026.
PID parameter set 2 is defined by parameters 4101...4126.
PID SET 1 is active.
Digital input DI1. 1 = PID SET 2, 0 = PID SET 1.
See selection DI1.
See selection DI1.
See selection DI1.
See selection DI1.
PID SET 2 is active.
SET 1, timed function 1 active = PID SET 2. See parameter
group
36 TIMED
FUNCTIONS.
TIMED FUNC
TIMED FUNC
TIMED FUNC
Inverted digital input DI1. 0 = PID SET 2, 1 = PID SET 1.
4005 ERROR VALUE INV
Wake-up level
when
4025
4025
Wake-up level
when
t
4023 PID SLEEP
and
4007 UNIT
LEVEL.
1.
1.
1.
Def/FbEq
0
settings.
4005
= 1
4005
= 0
LEVEL.
0.50 s
1 = 0.01 s
SET 1
0
1
2
3
4
5
7
8
9
10
11
-1