320 Fieldbus control with embedded fieldbus

DCU communication profile

Because the DCU profile extends the control and status interface to 32 bits, two
different signals are needed for both the control words
words
(0303
and 0304).
Control words
The following tables describe the Control word content for the DCU profile.
DCU profile Control word, parameter
Bit
Name
0
STOP
1
START
2
REVERSE
3
LOCAL
4
RESET
5
EXT2
6
RUN_DISABLE
7
STPMODE_R
8
STPMODE_EM
9
STPMODE_C
10
RAMP_2
11
RAMP_OUT_0
Value
Information
1
Stop according to either the stop mode parameter (2102) or
the stop mode requests (bits 7 and 8).
Note: Simultaneous STOP and START commands result in
a stop command.
0
No operation
1
Start
Note: Simultaneous STOP and START commands result in
a stop command.
0
No operation
1
Reverse direction. The direction is defined by using the
XOR operation on bit 2 and 31 (= sign of the reference)
values.
0
Forward direction
1
Enter local control mode.
0
Enter external control mode.
-> 1
Reset.
other
No operation
1
Switch to external control EXT2.
0
Switch to external control EXT1.
1
Activate Run disable.
0
Activate Run enable.
1
Stop along currently active deceleration ramp (bit 10). Bit 0
value must be 1 (STOP).
0
No operation
1
Emergency stop. Bit 0 value must be 1 (STOP).
0
No operation
1
Coast to stop. Bit 0 value must be 1 (STOP).
0
No operation
1
Use acceleration/deceleration ramp pair 2 (defined by
parameters 2205...2207).
0
Use acceleration/deceleration ramp pair 1 (defined by
parameters 2202...2204).
1
Force ramp output to zero.
0
No operation
(0301
and 0302) and status
0301 FB CMD WORD 1