198 Actual signals and parameters
All parameters
No.
Name/Value
1302 MAXIMUM AI1 Defines the maximum %-value that corresponds to
-100.0...100.0% Value in percent of the full signal range.
1303 FILTER AI1
0.0...10.0 s
1304 MINIMUM AI2
-100.0...100.0% See parameter
1305 MAXIMUM AI2 Defines the maximum %-value that corresponds to
-100.0...100.0% See parameter
1306 FILTER AI2
0.0...10.0 s
Description
maximum mA/(V) signal for analog input AI1. When used as
a reference, the value corresponds to the reference
maximum setting.
=
0...20 mA
0...100%
=
4...20 mA
20...100%
=
-10...10 mA
-50...50%
Example: If AI1 is selected as the source for external
reference REF1, this value corresponds to the value of
parameter
1105 REF1
Example: If the maximum value for analog input is 10 mA,
the percent value for 0...20 mA range is:
(10 mA / 20 mA) · 100% = 50%
Defines the filter time constant for analog input AI1, ie the
time within which 63% of a step change is reached.
%
100
63
Time constant
Filter time constant
Defines the minimum %-value that corresponds to minimum
mA/(V) signal for analog input AI2. See parameter
MINIMUM
AI1.
1301 MINIMUM
maximum mA/(V) signal for analog input AI2. See
parameter
1302 MAXIMUM
1302 MAXIMUM
Defines the filter time constant for analog input AI2. See
parameter
1303 FILTER
Filter time constant
MAX.
Unfiltered signal
Filtered signal
t
AI1.
AI1.
AI1.
AI1.
Def/FbEq
100.0%
1 = 0.1%
0.1 s
1 = 0.1 s
1.0%
1301
1 = 0.1%
100.0%
1 = 0.1%
0.1 s
1 = 0.1 s