ABB ACS355 User Manual page 225

Hide thumbs Also See for ACS355:
Table of Contents

Advertisement

All parameters
No.
Name/Value
2203 DECELER
TIME 1
0.0...1800.0 s
2204 RAMP SHAPE
1
0.0 = LINEAR
0.1...1000.0 s
Description
Defines the deceleration time 1, ie the time required for the
speed to change from the value defined by parameter
MAXIMUM FREQ
(in scalar control) /
SPEED
(in vector control) to zero. The control mode is
selected by parameter
• If the speed reference decreases slower than the set
deceleration rate, the motor speed will follow the
reference signal.
• If the reference changes faster than the set deceleration
rate, the motor speed will follow the deceleration rate.
• If the deceleration time is set too short, the drive will
automatically prolong the deceleration in order not to
exceed drive operating limits.
If a short deceleration time is needed for a high inertia
application, the drive should be equipped with a brake
resistor.
Actual deceleration time depends on parameter
RAMP SHAPE 1
setting.
Time
Selects the shape of the acceleration/deceleration ramp 1.
The function is deactivated during emergency stop and
jogging.
0.0: Linear ramp. Suitable for steady acceleration or
deceleration and for slow ramps.
0.1...1000.0 s: S-curve ramp. S-curve ramps are ideal for
conveyors carrying fragile loads, or other applications where
a smooth transition is required when changing from one
speed to another. The S-curve consists of symmetrical
curves at both ends of the ramp and a linear part in
between.
A rule of thumb:
A suitable relation between the ramp shape time and the
acceleration ramp time is 1/5.
Speed
Max
Par.
Actual signals and parameters 225
2002 MAXIMUM
9904 MOTOR CTRL
Linear ramp: Par.
2204
S-curve ramp:
Par.
2204
2202
Par.
2204
Def/FbEq
5.0 s
2008
MODE.
2204
1 = 0.1 s
0.0 =
LINEAR
1 = 0.1 s
= 0 s
> 0 s
t