GE 68K System User Manual page 18

System monitor
Table of Contents

Advertisement

GE Energy Services
Error Messages,
Message Summary (continued)
NVRAM invalid!
Protected process!
Record error!
Suspend all processes
first!
Test failed!
Using the 68K Monitor it is possible to modify or change something in a device's
If You Find
Yourself in
system that can seriously disrupt the operation of the device
Serious
Use this procedure to restore the RTU to its former state, before you used the 68K
Trouble...
Monitor facility to make changes.
Step
1.
2.
3.
4.
1-8
Continued
This Message
the query RAM (QR) command specified NVRAM is
but it is corrupt.
attempting to suspend (SP) a critical system process.
an invalid record is detected during the download
function (DL).
attempting a download without suspending all processes
first.
a system error is detected.
Suspend all processes in the RTU.
Fill the NVRAM memory with zeros.
Re-download your configurations and/or Flash code.
Reboot the RTU.
SWM0023 1.00 2
68K System Monitor
is displayed when...
Action
User's Guide
General
Full Release

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents