5865-3 / 5865-4 Led Annunciator Installation; 1: Facp Connection - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

5865-3 / 5865-4 LED Annunciator Installation

4.14 5865-3 / 5865-4 LED Annunciator Installation
The 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30 mappable LEDs, remote fire system silence and fire system reset key
switches, and a general system trouble LED. The 5865-3 has 30 mappable LEDs only. These are arranged as 15 pairs of red (typically used
for alarm) and yellow (typically used for trouble) LEDs.
Installation of the 5865-3 and 5865-4 is identical. The keyswitches and the trouble LED follow the behavior of other system annunciators
and do not require any installation steps. The following sub-sections describe how to install the 5865-3 and 5865-4 hardware. Refer to
Section 8 for programming information.
NOTE: This manual uses "5865" when referring to aspects of the 5865-3 and 5865-4 that are common to both models.
Note: Numbers indicate point
numbers for 5865. They do not
appear on board assembly.
Note: 5865 switches
follow the main FACP, no
installation or
programming required.
4.14.1 FACP Connection
The 5865 connects to the panel via the SBUS. Make connections as shown below. After the 5865 is connected to the panel, it must be added
to the system. This programming step is described in Section 8.2.2.
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
1
2
11
12
14
3
4
13
5
6
15
16
7
8
17
18
9
10
19
20
5865-4 Board Assembly
Figure 4.38 5865-3 and 5865-4 Assembly (Front View)
FACP
EXT. COMM
Figure 4.39 5865 Connection to the FACP
Plexiglass plate mounted to the LED
board at the factory.
Do not remove.
21
22
SILENCE
24
23
25
26
TROUBLE
27
28
29
30
RESET
5865
supervised,
power-limited Class B
Control Panel Installation
5865-3 Board Assembly
47