5815XL Installation

8.
Place the trim ring over the back box as shown below.
9.
Attach the door assembly to the backbox using the screws provided. Refer to Figure 4.25.
4.9.2 6860 Connection to the Panel
Connect the 6860 to the panel as shown below.
4.10 5815XL Installation
The 5815XL SLC expander lets you add additional addressable SD devices. The maximum number of SD SLC devices per panel is 635. The
number of 5815XL modules is limited by the maximum number of SBUS devices.
NOTE: 5815XL will only support SD protocol devices on this panel.
To install the 5815XL:
1.
Make sure power is off at the panel.
2.
Mount the 5815XL in the 6820 cabinet, the 5895XL cabinet, or the 5815RMK remote mounting kit. Use the standoffs located under the
control panel board assembly and secure with screws provided with the 5815XL. For additional information, see the 5895XL
Installation Manual or the 5815RMK Installation Instructions.
3.
Connect the 5815XL to the control panel. (See Figure 4.29.)
4.
Use onboard DIP switches to select an SBUS ID#. (See Section 4.15.1.)
5.
Add the 5815XL module to the system through programming. JumpStart will add the module automatically (see Section 7.1). You can
also add it manually (see Section 8.2.2). Select a name, if desired (see "Naming Modules" on page 91).
You are now ready to connect SLC devices to the 5815XL (see Section 8.5.1).
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Figure 4.26 Installing Trim Ring
FACP
Figure 4.27 6860 Connection to the Panel
supervised,
power-limited
Control Panel Installation
6860
41