8.5.4 Point Programming for 5880/5865 Modules
To program the 5880/5865 module output points:
1.
Login to the panel. The panel will automatically go to the Main Menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter Point Menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 7.5 for available choices. Then press ENTER.
5.
Enter the point number, then press ENTER.
6.
Press the up or down arrow key to select the type (notification or unused)., then press ENTER.
7.
Press the up or down arrow key to select the desired group., then press ENTER.
8.
Press ENTER to edit point name. See Appendix A. Or, Press right arrow key to skip point name edit.
9.
Repeat Steps 1 through 8 for all output points.
Select the circuit to program.
Select a name for the point.
10. To use 5880 as Input point, Enter point number 41 - 48. Then press ENTER.
11. Press the up or down arrow key to select type (switch or unused), then press ENTER.
12. Press the up or down arrow key to select the desired function, then press ENTER.
13. If the point supports latching press the up or down arrow key to select latching or non-latching, then press ENTER.
14. Press the up or down arrow key to select the desired group/zone, then press ENTER.
15. Edit point name Or Press right arrow key to skip module name edit.
16. Repeat steps 10 through 15 for all input points.
Select the point to program.
Select a name for the point.
8.5.5 Point Programming for the 5496
To program module points:
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Function Selections
Type Selections
B DETECT
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
A DETECT
2-WIRE SMOKE
4-WIRE SMOKE
CO 4-WIRE DET
CO 4-WIRE SUP DET
Table 8.6 Menu Choices for Internal/External Power Module (Continued)
M01 P001 NOTIF
MODULE_1 CKT_1
<Enter Pt or <=Exit>
Figure 8.3 Programming Output Points Screen for 5880 and 5865 Modules
M01 P048 SWITCH
MODULE_1 CKT_1
<Enter Pt or <=Exit>
Figure 8.4 Programming Input Points Screen for 5880 and 5865 Modules
for each Type
Used for Class B, 2-wire detectors.
Used for Class B, 4-wire detectors.
Used for Class B, 4-wire CO detectors.
Latching or Non-latching used for Class B, 4-wire CO Supervisory
detectors
Used for Class A, 2-wire detectors.
Used for Class A, 4-wire detectors.
Used for Class A, 4-wire CO detectors.
Latching or Non-latching used for Class A, 4-wire CO Supervisory
detectors
Group or Zone selection will appear depending on the type selected.
See Appendix A.
G01
Z001
Comments
Select NOTIF or UNUSED.
Select an output group for this notification point.
Select SWITCH or UNUSED.
Select an input zone.
Programming