2: View Group Points; 3: Edit Opg Template; Point; 1: Point Programming For 5815Xl Module - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

Point

Silencing Options
The following silencing options are available for each output group.
Optional Timers
Silence Inhibit
Auto Silence
Auto Unsilence
Startup Delay
8.4.2 View Group Points
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter group menu.
4.
Press 2 to view group points.
5.
Enter the group number, then press ENTER.
8.4.3 Edit OPG Template
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Press 3 to enter group menu.
4.
Press 3 to edit OPG Template.
5.
Enter the Template number, then press ENTER
6.
Press ENTER on the template name to edit the name.
You can use words to display a descriptive name for a group.
NOTE: See Appendix A for editing names.
7.
Right arrow to the OPG and select YES or NO to select which output groups to include in the template.
8.5 Point
You may need to change characteristics of individual input points (detectors and switches) even after using JumpStart AutoProgramming.
This section explains how to change options for: type of input point; latching/non-latching status (switches); and name and zone/group
assignment of a point.
8.5.1 Point Programming For 5815XL Module
To program for points on an 5815XL module, follow these steps:
1.
Login to the panel. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 7.5 for available choices. Then press ENTER.
5.
Enter the number of the point you wish to edit, then press ENTER.
6.
Select the type of device by pressing the up or down arrow key. Refer to the table under the column heading "Type Selection" for a list
of choices.
Type
Selection
UNUSED
DETECTOR
PHOTO
ION
HEAT
PHOTO DUCT
ION DUCT
2-WIRE SMOKE
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Timed Silence after Inhibit. If this option is selected, the output group must be audible for a programmed number of
minutes before it can be silenced. If the condition that caused the output to activate has not cleared during the time-frame,
the output can be silenced. If you select this option, select the timeframe in the delay field. Range is 0-60 minutes.
Silenceable. The output group will automatically silence after the timer expires. Range is 0-60 minutes.
If this option is selected, the output group can be silenced for a programmed time-frame. If the condition that caused the
output to activate has not cleared during the time-frame, the output reactivates. If you select this option, select the time-
frame in the delay field. Range is 0-60 minutes.
When an alarm is generated, the output group will not activate until the timer expires assuming the event is still active.
Range is 0-120 Seconds.
Table 8.3 Silencing Options
Function
Latching Option
Table 8.4 Programming Options for 5815XL Modules
Description
Select for SLC points that are unused.
Spot photoelectric detectors.
Spot ionization detector.
Spot heat detector.
Duct photoelectric detector.
Duct Ion detector.
2-wire smoke detector.
Comments
Programming
95

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820evs