Zone; 1: Edit Zone - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

Programming
4.
Press 4 to view list. Use the up or down arrow key to scroll though list.

8.3 Zone

Through the zone option in Panel Programming you can edit and view zone points. Selections made here affect all detectors and switches in
the zone. Up to 999 zones can be used in each panel.
8.3.1 Edit Zone
Features that can be edited through the Edit Zone option are zone name, zone properties (which includes, zone type, and detector sensitivity),
zone output mapping, and zone accessory options.
To edit a zone, follow these steps:
1.
Login to the panel.
2.
Select 7 for Program Menu.
3.
Press 2 to enter Zone Menu.
4.
Press 1 to edit a zone.
5.
Enter the zone number, then press ENTER.
Edit Zone Name
6.
Press 1 to edit the selected zone name. You can use words to display a descriptive name for a zone.
NOTE: See Appendix A for editing names.
Edit Zone Properties
Zone properties consist of alarm delay characteristics, and heat detector sensitivity.
1.
Do steps 1 through 5 of Section 8.3.1.
2.
Press 2 to edit the properties of the selected zone.
Zone number being
programmed
Alarm Delay Characteristics
The programmed zone type is provided for user reference only. Use HFSS to modify the zone type.
Table 8.2 lists the alarm delay characteristics and a description of each.
Type of Delay
1
1-Count
2-Count
Alarm Verification
92
Z001-Type:1-Count___
Heat [150]F.
Figure 8.2 Edit Zone Properties
One Count (No Delay). When this option is enabled, an alarm occurs immediately when a single device of any of the
following types goes into alarm: detector, manual pull, water flow, Aux1 or Aux2. This is considered the most typical
operation and is the default for all zones.
When this type of alarm delay is used, two or more detectors within the zone must go into alarm in order for the zone to
report an alarm. Switches of type manual pull, water flow, Detector Switch, Aux1 and Aux2 are an exception; they will
cause an alarm when only one switch is in alarm.
When a single detector is in alarm in a 2-Count zone, the system enters a pre-alarm condition. In a pre-alarm condition,
the touchpad PZT beeps and the annunciator display indicates that a pre-alarm has occurred. If the zone has been
mapped to an output group for the pre-alarm event, the output group will activate. The pre-alarm will not be reported to
the central station.
Alarm verification is an optional false alarm prevention feature that verifies an alarm condition by resetting the smoke
detector. If the alarm condition still exists by the time the reset cycle has completed, the detector will go into alarm. If the
detector is no longer in alarm, no report will go to the central station. The alarm verification sequence is ignored if the
zone is already in alarm.
Description
Table 8.2 Alarm Delay Types
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Detection type also selected from this screen
(see Table 8.2).
Select the temperature that will cause heat
detectors in this zone to go into alarm.
Range: 135°-190° (SK devices)
135°-150° (SD devices)
Zone

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820evs

Table of Contents