2: Point Programming For 6815 Module - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

Point
Type
Selection
SWITCH
DETECTOR
(cont.)
FIRE TAMPER
MANUAL
RELEASE
INTERLOCK
STATUS POINT
EVS INPUT
EVS TAMPER
EVS SUPER-
VISORY
CO DETECT
SWITCH
CO
SUPERVISORY
DETECT SWITCH
NOTIF
OUTPUT PT
AUX CONST
AUX RESET
AUX DOOR
RELAY
OUTPUT PT
AUX RESET
AUX DOOR
SLC LED
LED NUMBER
LED FUNCTION
8.5.2 Point Programming For 6815 Module
To program for points on an 6815 module, follow these steps:
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 7 for Panel Programming.
3.
Press 4 to enter Point Menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 7.5 for available choices. Then press ENTER.
5.
Select S for sensor or M for module. (SK devices only)
6.
Enter the number of the point you want to edit, then press ENTER.
7.
Select the type of device by pressing the up or down arrow key. Refer to the table below under the column heading "Type Selection" for
a list of choices.
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Function
Latching Option
Latching
Non Latching
Latching
Non Latching
Latching
Non Latching
Latching
Non Latching
Latching
Non Latching
Select Group
Select Group
01-80
Unused
NOTIF
Table 8.4 Programming Options for 5815XL Modules (Continued)
Used to monitor conventional 4-wire detectors, a contact closure will generate a
detector alarm event.
Performs identically to a supervisory switch, but will be indicated as a tamper
switch on the LCD annunciator.
Manual release switch
Interlock release switch input.
User also has EVS Event Number 1-8 option for EVS INPUT.
Only available when an EVS-VCM is installed in the system.
CO Detector Switch
CO Supervisory Detector Switch
Output point, a general use notification type. Use for driving standard notification
appliances.
Use constant power for applications that require a constant auxiliary power
source. Power is always present at constant circuits.
Use for auxiliary power, resettable applications. See Section 4.17.5 for a
description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you were using
an auxiliary power supply for door holders, you would use this option. See Section
Door Holder Power for a description of how this option operates.
Output point, a general use relay type. Use for applications requiring a relay, such
as fan shutdown, elevator recall, and so on.
Use for auxiliary power, resettable applications. See Section 4.17.5 for a
description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you were using
an auxiliary power supply for door holders, you would use this option. See "Door
Holder Power" on page 54 for a description of how this option operates.
For use with SD devices only. 80 sub addresses on LED.
Notification can have group number.
Comments
Programming
97

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820evs