System Operation
9.8.4 Using a Recorded F-Key Macro
1.
From the idle screen on any annunciator in the site, press the F-Key you want to activate.
2.
Once finished, to deactivate the macro press the F-Key again.
9.8.5 F-Key Status Event
When an F-Key is enabled, it activates its corresponding F-Key Active event. This is a status type event that can activate outputs without
showing any status on annunciator displays. This should be used for ancillary purposes only.
9.8.6 F-Key Map Inhibit
The F-Keys have the ability to disable event - output group mapping for the purpose of simulating that the map doesn't exist. This can be
setup to allow for testing purposes where notification of an entire building is not desired during the test. This option is programmable for
each output group map through HFSS.
When an F-Key is active and a map in the system is set to be disable by Map Inhibit, the system will show a trouble event indicating it as
such.
126
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Function Keys