2: Banner; Menu System; 1: Panel Login Menu - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

System Operation
9.1.2 Banner
The banner is the message that displays on the control panel when the system is in normal mode (no alarm or trouble condition exists and
menus are not in use). A customize message can be created that will display instead of the internal (default) message. See Section 8.6.5 for
information on editing the banner.
internal banner text
internal banner text
custom banner
example

9.2 Menu System

The control panel is easy to operate from the Main Menu. To view the Main Menu press the ENTER or right arrow key on the control panel
or remote annunciator. This will bring up the panel login menu, as described in Section 9.2.1. Once validated, the user will be able to access
the Main Menu as shown in Section 9.2.2. Select the desired option. You will be prompted for as access code if required.
The control panel supports up to 20 access codes. The profile for each access code (or user) can be modified through the network program-
ming option (see Section 6.2.5 for access code programming).
9.2.1 Panel Login Menu
After pressing ENTER, and 1 for the login menu, a screen will prompt for the type of access account, Administrator or User. An administra-
tor has the ability to modify user accounts and view the cybersecurity log. The User account has access to panel programming.
Admin Profiles
After initial power-up, the 6820 requires a password change and user account setup before programming. Only Admin1 will be active. Using
the login for Admin1, the default password (0000000) must be changed to a new, unique password. This new password must be 7-digits and
cannot be sequential or easily guessed. If the password is not changed, a default password trouble will appear on the panel.
There is a maximum of two administrator profiles available. After the administrator account is set up, you must create a User account(s).
Only a User account has the ability to program the control panel. There is a maximum of 18 User accounts available.
Admin accounts can:
View cybersecurity logs with date/time stamp
Edit name to user profiles
Enable/disable user profiles
Modify access codes of user profiles
Edit access to panel functions
Change computer access code
Restore factory default settings to the panel
User (Installer) Profiles
There are two programming levels which will access the Programming screens. From either of the screens, access to specific system and
device features or programming may be obtained. An "Installer" can program local panel data relating to device types, zoning, messages,
control panel functions, etc. A "Multi-site Installer" can program panel data across a network. A user has the ability to change their adminis-
trator-assigned password after it has been assigned for the first time. Refer to Section 6.2.5 on page 68.
Profile 1 is the profile used that dictates what functions to which the Fire Fighter Key has access. Because this is the profile used for a
key, the User Name and the Access Code cannot be edited.
112
Site 1
Silent Knight 6808
ALL SYSTEMS NORMAL
08/03/21 01:15:06PM
Figure 9.3 6820 Banner Display Examples
Silent Knight - Model 6820
ALL SYSTEMS NORMAL
08/03/21 01:15:06PM
ABC COMPANY - FIRE SYSTEM
ALL SYSTEMS NORMAL
08/03/21 01:15:06PM
Figure 9.4 6820EVS Banner Display Examples
custom banner
example
Site 1
Site 1
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Menu System
ABC Company
Fire System
ALL SYSTEMS NORMAL
08/03/21 01:15:06PM