AC Power Connection

0.25" spacing must be
maintained between each of
these circuit types, as well as
between power-limited and non-
power-limited circuits.
4.4 AC Power Connection
WARNING: RISK OF ELECTRICAL SHOCK AND EQUIPMENT DAMAGE
!
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF
POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR
INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED
The AC terminals are rated at 120VAC, 60Hz, 3.3A.

4.5 Battery Power

The batteries must be sealed lead acid type. Before connecting the batteries to the FACP, make certain that the interconnect cable between the
batteries is not connected. Do not connect the battery jumper cable until the system is completely installed. Observe polarity when connect-
ing the batteries.
WARNING: RISK OF PERSONAL INJURY
!
BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN
DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH
WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
AC power
SLC
battery
Figure 4.4 Wire Routing Example for 6820EVS
black
green
white
Figure 4.5 AC Power Connection
NAC/aux power circuits
relay circuits
SBUS
phone lines
battery
Control Panel Installation
29