Table C.1 shows the cadence patterns available for use with the control panel.
#
00
Constant
01
March Time
02
ANSI 3.41
03
Single Stroke
04
California
05
Zone-coded, Zone 1
06
Zone-coded, Zone 2
07
Zone-coded, Zone 3
08
Zone-coded, Zone 4
09
Zone-coded, Zone 5
10
Zone-coded, Zone 6
11
Zone-coded, Zone 7
12
Zone-coded, Zone 8
13
Zone-coded, Custom 1
14
Zone-coded, Custom 2
15
Zone-coded, Custom 3
16
Zone-coded, Custom 4
17
Sync Type- Faraday (N/A)
18
Sync Type- Gentex
19
Sync Type- System Sensor
20
Sync Type- Wheelock
21
Sync Type- AMSECO
22
Power Isolated
23
Temporal 4
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022

Appendix C: Cadence Patterns

Name
Continuous sound (This is the only pattern that can be used for relay circuits. The system will
override any other choice.)
0.5 second on, 0.5 second off
0.5 sec on, 0.5 sec off, 0.5 sec on, 0.5 sec off, 0.5 sec on, 1.5 sec off
0.1 sec on, 1 sec off, 0.1 sec on, 1 sec off, 0.1 sec on, 3 sec off
5 sec on, 10 sec off
0.5 sec on, 0.5 sec off
This pattern is multiplied by the zone number in alarm, followed by 3 seconds off.
For example, Pattern 6, Zone 2 coded: (pattern x two):
0.5 sec on, 0.5 sec off, 0.5 sec on, 0.5 sec off, 3 sec off
These outputs provide synchronization for Gentex, System Sensor, Wheelock, or AMESECO
synchronized appliances.
Disconnected. No voltage at terminals.
0.1 sec on, 0.1 sec off, 0.1 sec on, 0.1 sec off, 0.1 sec on, 0.1 sec off, 0.1 sec on, 5 sec off,
Pattern Description (Patterns repeat until condition is cleared.)
Table C.1 Cadence Patterns