10: Reset Alarms; 11: Check Detector Sensitivity Through Point Status - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

System Operation
NOTE: Multi-site displays do not allow for silencing multiple sites. Pressing SILENCE will only locally silence the PZT built into the annunciator.
NOTE: For EVS systems, pressing silence at an LOC will only silence the system in control. See Section 9.4.1.
9.3.10 Reset Alarms
Press RESET to perform a control panel reset. If an external reset switch has been installed, activating the switch will reset fire alarms.
NOTE: Multi-Site displays do not reset multiple sites.
NOTE: For EVS Systems, pressing reset at an LOC will prompt the user for which system they want to reset. See Section 9.4.1.
Reset Communicator
This option allows the user to Reset the Communicator. The LCD will display:
"Resetting Communicator... Please Wait"
You will be returned to the Main Menu when the reset is complete.
The Communicator is not allowed to be reset when alarms or supervisories are active. Communicator Reset is not allowed if any of the fol-
lowing are active:
Fire Alarm
Fire Supervisory
Fire Pre-Alarm
CO Alarm
CO Supervisory
EVS Alarm
EVS Supervisory
9.3.11 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72. Detectors are sam-
pled every three hours.
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a Calibration Trouble condition. A detector enters a
Calibration Maintenance state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a Calibration Trouble condition occurs, the central station receives a detector trouble report ("373" + Zone # for Contact ID format;
"FT" + Zone # in SIA format).
To check sensitivity for an individual detector, follow the steps below.
1.
From the Main Menu, press 2 for Point Functions.
2.
Press 2 for Point Status.
3.
Select the module where the point you want to check is located.
4.
Enter the number of the point you want to check and press ENTER.
116
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022