Control Panel Installation
4.14.2 5865 Mounting
Mount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a standard 3-gang electrical box. In Figure 4.40, the 5865-4
attached to a 4-gang box, is used as an example.
cover plate
The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly. These labels can be used in a type-
writer or can be written on by hand. Slide the labels under the plexiglass as shown in Figure 4.41. The LEDs will show through the label
when illuminated.

4.15 Configuring SBUS Modules

This section describes how to configure any system hardware modules that have been added to the system.
4.15.1 Assigning SBUS Module IDs
SBUS devices on a panel are addressed from 1 to 63. Although the addressing scheme allows 63 SBUS devices to be connected to a panel,
the actual number is limited by current draw and SBUS bandwidth usage as discussed below. When installing a hardware module (see
Table 4.1 for a list of compatible devices), you must use the DIP switches on the module to assign an ID number to the module. Address zero
is an invalid address and is not allowed.
48
Attach the 5865 to a
standard 3- or 4-gang
electrical box.
Figure 4.40 5865 Mounting Example
TOP
Zone 1
1st Flr South
Zone 2
1st Flr West
Zone 3
2nd Flr West
Zone 4
2nd Flr East
Zone 5
3rd Floor
Figure 4.41 Inserting Zone Description Labels
The 5865 is mounted to a
plexiglass plate at the factory.
SILENCE
TROUBLE
RESET
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Configuring SBUS Modules