Point
Type Selection
SWITCH
(cont.)
NOTIF
RELAY
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Function
Latching Option
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
Latching
Non Latching
ZONE AUX2
Latching
Non Latching
SYSTEM AUX1
Latching
Non Latching
SYSTEM AUX2
Latching
Non Latching
DETECTOR
FIRE TAMPER
Latching
Non Latching
MANUAL RELEASE
INTERLOCK
STATUS POINT
EVS INPUT
Latching
Non Latching
EVS TAMPER
Latching
Non Latching
EVS
Latching
SUPERVISORY
Non Latching
CO DETECT SWITCH
CO SUPERVISORY
Latching
DETECT SWITCH
Non Latching
TROUBLE_MON
OUTPUT PT
Select Group
AUX CONST
AUX RESET
AUX DOOR
OUTPUT PT
Select Group
AUX RESET
AUX DOOR
Table 8.5 Programming Options for 6815 Modules (Continued)
This system-level switch is an alternative way to silence the fire system. It has
the same effect as pressing the Silence key.
This system-level switch is an alternative way to reset the fire system. It has
the same effect as pressing the Reset key.
Positive acknowledge switch. This switch must be used in zones programmed
as Positive Alarm Sequence (see "Edit Zone Properties" on page 92).
If an acknowledge switch closes when an alarm or trouble condition is not
already in progress, a trouble will occur.
You must use a UL listed normally open, momentary switch type. The switch
must be rated at 5V, 100 mA (minimum) and be used with an EOL resistor for
supervision.
Use these switch types if you want to monitor special zone-level conditions
(such as dry contact from a remote power supply).
Use these switch types if you want to monitor special system-wide conditions
(such as dry contact from a remote power supply).
Used to monitor conventional 4-wire detectors, a contact closure will generate
a detector alarm event.
Performs identically to a supervisory switch, but will be indicated as a tamper
switch on the LCD annunciator.
Manual release switch
Interlock release switch input.
User also has EVS Event Number 1-8 option for EVS INPUT.
Only available when an EVS-VCM is installed in the system.
CO Detector Switch
CO Supervisory Detector Switch
Use this switch type to monitor trouble from external devices. Trouble
monitors are used in HVAC operations.
Output point, a general use notification type. Use for driving standard
notification appliances.
Use constant power for applications that require a constant auxiliary power
source. Power is always present at constant circuits.
Use for auxiliary power, resettable applications. See "Resettable Power" on
page 54 for a description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you were
using an auxiliary power supply for door holders, you would use this option.
See "Door Holder Power" on page 54 for a description of how this option
operates.
Output point, a general use relay type. Use for applications requiring a relay,
such as fan shutdown, elevator recall, and so on.
Use for auxiliary power, resettable applications. See "Resettable Power" on
page 54 for a description of how this option operates.
Use for auxiliary power, door holder applications. For example, if you were
using an auxiliary power supply for door holders, you would use this option.
See "Door Holder Power" on page 54 for a description of how this option
operates.