7.2.4 Mapping LED Points
Figure 7.6 is a simple example showing how LED points are mapped to zones and output groups. Typically you would create two output
groups for each zone, one for alarms and one for troubles. (LED points are available when models 5865-3/4 and/or 5880 are used with the
system).
Zone 1
manual pull alarm
Zone 1
detector alarm
Zone 1
trouble
Zone 2
manual pull alarm
Zone 2
detector alarm
Zone 2
trouble
Figure 7.6 Example of LED Points Mapped to Output Groups (applies to Models 5865-3/4 and 5880)

7.3 Programming Using the HFSS Software Suite

You can use the HFSS Software Suite to program the control panel onsite (personnel will need to be onsite during the upload or download
process). HFSS is a software package that lets you easily program the control panel using a Windows-based computer. HFSS is needed for
Mapping. When using HFSS, you can set up the programming options for the panel, save the options in a file, then download the file to the
panel. You can connect to the control panel directly using the onboard USB or Ethernet. Updates are available at www.silentknight.com.
78
Group 3
3rd floor
notification
Group 2
2nd floor
notification
ANSI 3.41
Group 1
1st floor
ANSI 3.41
notification
constant
Figure 7.5 Example of Zone Events Mapped to Output Groups and Patterns
Mapping LEDs to Zones and Output Groups
Zone 3
Offices
3rd floor
Zone 2
Storage
2nd floor
Zone 1
Show Room
1st floor
Output group 1
red LED 1
An alarm in Zone1 will activate red
LED1 and any other required outputs.
alarm outputs
(horns, strobes, etc.)
Output group 2
A trouble in Zone1 will activate yellow
yellow LED 2
LED2 plus any other needed outputs.
(In this example, it activates a sounder in
maintenance room
the maintenance room.)
sounder
Output group 3
red LED 3
An alarm in Zone2 will activate red
LED3 and any other required outputs.
alarm outputs
(horns, strobes, etc.)
Output group 2
yellow LED4
A trouble in Zone2 will activate yellow LED4.
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Programming Using the HFSS Software Suite
Group 3
3rd floor
notification
ANSI 3.41
Group 2
manual pull
2nd floor
ANSI 3.41
notification
detector alarm
constant
supervisory
Group 1
notification
1st floor