H-S81-HS
INDUSTRIAL FIRE PANEL
INSTALLATION & OPERATION MANUAL
P/N LS10114-000HI-E:A • ECN 15-xxx • 2/24/2015

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell H-S81-HS

  • Page 1 H-S81-HS INDUSTRIAL FIRE PANEL INSTALLATION & OPERATION MANUAL P/N LS10114-000HI-E:A • ECN 15-xxx • 2/24/2015...
  • Page 2 Adequate written records of all inspections (especially in bedrooms), smoking in bed, and violent explosions should be kept. Limit-D-1-2013 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 3 ©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 4 •Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 5: Table Of Contents

    Battery Charger Section ........................32 Cooling Unit ............................32 Protections ............................32 Reference Standards ..........................32 Possible Configurations........................33 2.1.5: PU-A0007-1 Drawer with Slots ......................33 Description ............................33 Internal connections..........................34 2.1.6: PU-A0008-1 Power Supply Module....................35 Description ............................35 Technical Features..........................36 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 6 Zero Point Calibration ..........................51 End of Scale Calibration........................51 Field Connections ..........................51 Standard Connection Diagrams ......................52 2.4.3: S81-F4002-1 & S81-F4002-2 ......................53 Description............................53 Technical Features ..........................53 Status Indications..........................53 Three-Digit Display ..........................53 Configuration............................54 Threshold Setting ..........................54 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 7 Description ............................69 Technical Features..........................69 Status Indications..........................69 Virtual channels............................69 Configuration............................70 Field Connections..........................70 2.4.10: S81-F6002-1 ............................71 Description ............................71 Technical Features..........................71 Configuration............................71 Logic Functions ............................71 Field Connections..........................73 2.4.11: S81-F7002-1 ............................73 Description ............................73 Technical Features..........................73 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 8 Programming the Weighing Module Address ..................91 Weighing Module Reset ........................91 2.5: Termination modules............................91 2.5.1: S81-T8001-1 ............................92 Description............................92 Technical Features ..........................92 Field Connections ..........................93 2.5.2: S81-T8003-1 ............................93 Description............................93 Technical Features ..........................93 Field Connections ..........................93 2.5.3: S81-T8005-1 ............................94 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 9 Section 3: Installation......................105 3.1: Positioning of the Control Panel........................105 3.2: Measures for Installation in Compliance with the EC Standard..............105 3.3: Mounting the H-S81-HS-1R & H-S81-HS-2R Control Panels ..............105 3.4: Positioning the H-S81-HS-1/10R Control Panel ..................106 3.5: Layout of H-S81-HS/1R Internal Parts......................107 3.6: Layout of H-S81-HS/2R Internal Parts......................108...
  • Page 10 6.2.16: Out of Service Condition .......................124 6.2.17: Release Signal Delay ........................124 6.2.18: Signal Representing Extinguishing Agent Flow................124 6.2.19: Emergency Hold ..........................125 Mode-A...............................125 Mode-B ...............................125 6.2.20: Activation of a Secondary Release Sequence................125 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 11 7.9: Operations at Access Level 3 ........................140 7.10: Configuration ............................140 7.10.1: 4-20mA Modules...........................140 7.10.2: Fire Extinguishing Modules ......................141 7.10.3: Communications..........................142 Printer ..............................142 Host Computer............................143 TCP-IP..............................144 7.10.4: Standard Options ...........................145 7.10.5: Change Password...........................146 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 12 C.1: H-S81-HS Control Panel Absorption ......................168 C.2: Absorption of Hochiki Conventional Detectors..................168 C.3: Absorption of Hochiki Addressable Devices ....................169 C.4: Absorption of Honeywell Addressable Devices ..................169 C.5: Absorption of Apollo Addressable Devices....................170 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 13 C.6: Absorption of System Sensor Addressable Devices .................171 C.7: External Load Absorption .........................172 C.8: Calculation of Total System Absorption ....................172 C.9: Calculation of Battery Capacity ........................172 Appendix D: Adhesive Labels ..................... 174 D.1: CPR Adhesive Label..........................174 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 14: General Information

    General Information Related Documentation For specific and detailed information on the H-S81-HS panel and system, please refer to following documents: Document number Name ST-058-IT Installation and user manual (this manual) ST-071-IT Safety Manual ED-Cxxxxx-Fyy-Rz Wiring diagram (specific to each control panel)
  • Page 15: Section 1: General Description

    It is characterized by easy configuration and programming, combined with excellent reliability and system diagnosis. The H-S81-HS is similar to a “safety PLC” and can be configured and programmed for carrying out integrated safety functions including fire prevention, gas detection, burglar alarm and technological control in compliance with applicable standards.
  • Page 16: Mechanical Structure

    Mechanical Structure 1.2 Mechanical Structure The H-S81-HS system is a modular unit consisting of 19” 3-unit high anodized aluminum racks; they will be installed in a metal cabinet with revolving rack and acrylic glass door. It can include a variable number of racks (2 to 11), according to the specific needs.
  • Page 17: General Features

    • Steelwork type: Metal, with transparent door and revolving inner door • Color: RAL 7032 • Protection class: IP30 • Type of installation: Floor ground installation • Dimensions: H=2100mm W=800mm D=800mm H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 18: 2: Electrical Characteristics

    SHOULD STORAGE TEMPERATURE BE LOWER THAN -30°C OR EXCEED +60°C, REMOVE THE LITHIUM BATTERY ON CENTRAL UNITS (S81-U1002-1 MODULES). 1.3.5 Mechanical Conditions The table below summarizes the type of mechanical tests undergone by the H-S81-HS system. Standard Test Test Levels...
  • Page 19: 6: Electromagnetic Compatibility (Ce)

    General Description 1.3.6 Electromagnetic Compatibility (CE) The H-S81-HS system has been designed and tested for resisting to standard levels of radiated and conducted electromagnetic interference, and electrostatic discharges. The table below lists the types and levels of the tests undergone by the H-S81-HS system.
  • Page 20: Duplex" Configuration

    Should it detect any faults, the module would set in safety condition. If there is a redundant CPU, the new CPU will carry out the monitoring functions without any interruptions. The broken CPU can be replaced without the need of switching off the system. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 21: 2: Digital Input Modules

    The broken module can be replaced without the need of switching off the system. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 22: 5: Central Unit Safety Switch-Off

    CPU, the secondary one signals primary CPU failure and starts controlling the system without any interruption of system operation. If, instead, the sequence is carried out only by the secondary CPU, the primary one signals secondary CPU failure and keeps carrying out its functions. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 23: Communication Network Between Control Panels

    Figure 1.8 Communication Network Between Control Panels H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 24: Communication Protocol For Supervisory Systems

    Undefined remote rule 1.7 Communication Protocol for Supervisory Systems H-S81-HS systems can be connected to IRIDE supervisory system via LAN network or point-to- point serial connection. A maximum of 2 supervisors per control panel can be configured on the LAN network, and one on Host serial port. In both cases, a dedicated protocol is used. The connec- tion between control panels and supervisors can be made of copper, optical fiber or copper/fiber (mixed), for meeting different needs.
  • Page 25: Opc Server

    Figure 1.10 Example of Connection with OPC Server 1.9 Programming H-S81-HS system programming is carried out through a personal computer in OFF-LINE mode by means of a specific configuration program. After completing the configuration and checking that the entered data are correct, data can be transferred to the central unit. Once they have been trans- ferred, the central unit replaces the old configuration with the new one and re-initializes the system.
  • Page 26 General Description Programming Figure 1.11 Configuration Program H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 27: Section 2: Parts Of The H-S81-Hs System

    Section 2: Parts of the H-S81-HS System This chapter provides a detailed description of all the parts making up the H-S81-HS system. 2.1 Power Supply Set The H-S81-HS control panel can be equipped with the following power supply sets: •...
  • Page 28: 2: Pu-A0005-1 Power Supply Module

    3000 VAC for 1 minute • Dielectric strength between input and ground: 1500 VAC for 1 minute • Output voltage: 25VDC • Max. output current: • Ripple: <266mV • Protections: Line Fuse, over-current, short circuit H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 29: Internal Connections

    RS232 port for the connection to a supervisory sys- tem. It can be used together with one or more PU-A0005-1 power supply units. In this case, the resulting power supply set will be fully compliant with the EN54-4:1997/A2:2006 standard. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 30: Technical Features

    RS232 port for the connection to the configuration program Test-PUA009. Ho-swapping is possi- ble for both the 4 AC/DC converters and the battery charger (Hot Plug). H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 31 Power Supply Set Parts of the H-S81-HS System Figure 2.2 S81-PU002 Power Supply Set - Front View Figure 2.3 S81-PU002 Power Supply Set - Rear View H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 32: Technical Features

    • Fan average life at 40° C 80,000 hours Protections • Line Fuse: T10A H 250V (5x20) • Protections: Over-voltage, short circuit and battery reverse polarity Reference Standards • EN54-4 • EN50081-2 • EN50082-2 • EN60950 (CEI-74-2) H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 33: Possible Configurations

    PU-A0008-1 power supply modules. It features ventilation, consisting in three fans with a diameter of 120 mm. The terminal blocks for power supply and status replication connection are located on slot back. Figure 2.4 S81-PU002 Power Supply Set Slot H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 34: Internal Connections

    Fan speedometer signal 4-5-6 Fan power supply negative Fan power supply positive Output voltage Terminal Name Function +VLOAD Supply voltage positive -VLOAD Supply voltage negative +VBAT Battery positive -VBAT Battery negative H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 35: 6: Pu-A0008-1 Power Supply Module

    LEDs signaling the proper presence of input and output voltage; a yellow LED that lights up in case of failure; and a button for shutting the module down before hot-swapping. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 36: Technical Features

    It is used together with one or more PU-A0008-1 power supply units. In this case, the resulting power supply set is fully compliant with the EN54-4:1997/A2:2006 standard. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 37: Technical Features

    I/O control. It has the function of processing the data received from the modules and controlling the operator interface and the communication with supervisory systems. Figure 2.6 Central Unit Rack H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 38: 1: S81-E2003-1

    (Bus-IN) must be connected to the BUS-OUT terminal of the last rack, whereas the J3 con- nector (Bus-OUT) must be connected to the BUS-IN terminal of the first rack. Figure 2.8 RJ45 UTP Connection Cable H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 39: 2: S81-U1002-1

    • Supply voltage: 22-29VDC • Quiescent current: 70mA • Operating temperature: -5 - 50 °C • Storage temperature: -30 - 80 °C • Maximum humidity: 95% (RH) non-condensing • Hot swap capability: H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 40: Status Indications

    The display module is the interface between the control panel and the operator. It includes a LED- backlit graphic display with 30 lines of 52 characters each, 19 LEDs, 23 buttons, and one buzzer. Figure 2.10 S81-U1006-1 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 41: Technical Features

    System sounder silencing Silencing of system fire alarm sounders Control panel reset Resets the control panel Evacuation command Activates system fire alarm sounders Delay time reset 1-2-3 Cancels output delay timer H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 42: Internal Connections

    A 10-pole connector connecting the membrane keyboard to the display. 2.3 I/O Rack Up to ten expansion racks can be connected to an H-S81-HS base. Each can include up to thirteen I/O modules. Position 14 is reserved to the S81-E2002-1 rack controller. Two I/O rack types are available according to the type of terminations to be used.
  • Page 43: 1: S81-E2001-1

    Field devices, in this case, can be easily disconnected by simply disconnecting the flat cables from the termination modules. 20-Pin Ribbon Cable Connection on Rear Rack Termination module on DIN rail Figure 2.13 Flat Cable Connections H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 44: 2: S81-E2001-2

    Pre-wired cables are used in this case to connect the rack to the terminal block. Standard cable length is 2 meters. The cable type and the relevant connections depend on the type of module to be terminated. Figure 2.15 Multi-conductor Cable Connections H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 45: 3: S81-E2002-1

    Redundancy not possible S81-F4002-2 Module with 2 4-20mA analog inputs Redundancy possible S81-F4003-1 Module with 8 x 4-20mA analog inputs Redundancy not possible S81-F4003-2 Module with 8 x 4-20mA analog inputs Redundancy possible H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 46: 1: S81-F3002-1 & S81-F3002-2

    − ∅ Tampering − ∅ −−− −−− Pre-alarm − ⊗ − ⊗ Alarm Key to symbols: ⊗= steady on LED; − = LED off, ∅= flashing LED, −−−= function not available H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 47: Configuration

    20-way flat cable.  S81-E2001-2 Bus The module is connected to the field terminal block by the S81-CCT6 16- conductor multi-polar cable. For S81-F3002-2 module redundant connec- tion, use the S81-CCT1R cable. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 48: Standard Connection Diagrams

    Figure 2.16 Field connections Standard Connection Diagrams Figure 2.17 Standard Connection Diagram of NO/NC Contacts Figure 2.18 Standard Connection Diagram of Conventional Detectors Figure 2.19 Standard Connection Diagram of the Intrinsic Safety Barrier H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 49: 2: S81-F4001-1 & S81-F4001-2

    Pre-alarm ⊗ − − Alarm Key to symbols: ⊗= steady on LED; − = LED off; ∅= flashing LED  LED Bar It indicates the 0-100% percentage of the measured value. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 50: Configuration

    3: • Pre-alarm threshold. • Alarm threshold • Current value below which a trouble condition is signaled • Calibration mixture concentration value for end of scale calibration H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 51: Zero Point Calibration

    20-way flat cable.  S81-E2001-2 Bus The module is connected to the field terminal block with the S81-CCT2 16- conductor multi-polar cable. For S81-F4001-2 module redundant connection, use the S81-CCT2R cable. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 52: Standard Connection Diagrams

    Termination with Multi-conductor Cable ∅ Input signal White ∅ ∅ ∅ ∅ Output signal Brown ∅ ∅ S81/CCT2 ∅ S81-T8003-1 S81/CCT2R Figure 2.21 Field Connections Standard Connection Diagrams Figure 2.22 Standard Connection Diagram H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 53: 3: S81-F4002-1 & S81-F4002-2

    1 For current values lower than the set trouble threshold and exceeding 1mA, the display will show the value of the measured current in mA preceded by letter F. Please refer to the manual of the connected device for identifying the type of anomaly. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 54: Configuration

    Press the “4” key to cancel the operation for the channel 2. • Exit the module diagnosis cycle and enable the channel. NOTE: The zero point can be calibrated only with zero values ranging between 3 and 5mA. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 55: End Of Scale Calibration

    20-way flat cable.  S81-E2001-2 Bus The module is connected to the field terminal block with the S81-CCT7 16- conductor multi-polar cable. For S81-F4002-2 module redundant connection, use the S81-CCT7R cable. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 56: Standard Connection Diagrams

    Input signal 2 Brown ∅ ∅ Output signal 1 Green ∅ S81/CCT7 ∅ Output signal 2 Yellow ∅ S81-T8003-1 S81/CCT7R Figure 2.23 Field Connections Standard Connection Diagrams Figure 2.24 Standard Connection Diagram H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 57: 4: S81-F4003-1 & S81-F4003-2

    Enable/Disable commands from Hosts on the channel No, TCP1, TCP2, RS232 It defines the format of the analog value sent via ModBus, mA, mA tenth, VI, VI tenth, converter points and automatically via Host H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 58: Threshold Setting

    ±3mA than the set calibration value. Field Connections The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 59: Standard Connection Diagrams

    Input signal 5 ∅ Pink Input signal 6 S81/CCT3 ∅ Blue Input signal 7 ∅ S81/CCT3R Input signal 8 S81-T8003-1 Figure 2.25 Field Connections Standard Connection Diagrams Figure 2.26 Standard Connection Diagram H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 60: 5: S81-F5001-1 & S81-F5001-2

    Output status in case of CPU fault Frozen in the last status / Off Enable/Disable status export to Hosts No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts No, TCP1, TCP2, RS232 on the channel H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 61: Field Connections

    Output 2 ∅ Green Output 3 ∅ Yellow Output 4 ∅ Gray Output 5 ∅ Pink Output 6 S81/CCT3 ∅ Blue Output 7 ∅ S81/CCT3R Output 8 S81-T8003-1 Figure 2.27 Field Connections H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 62: Standard Connection Diagrams

    Each one of the sixteen channels on the front panel includes a status LED. Indications 1-16 Out LEDs Output Channel Status RED LED − Channel under normal condition ⊗ Enabled channel ⊗= steady on LED; − = LED off H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 63: Configuration

    SELV voltage.  S81-E2001-2 Bus Thanks to this bus, the module can be terminated by using a S81-CCT1 16-conductor multi-polar cable or a S81-T8007-2 16-relay module. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 64: 7: S81-F5003-1

    Yellow LED RED LED − − ⊗ − Disabled ∅ − Trouble − ⊗ Active Key to symbols ⊗= steady on LED; − = LED off; ∅= flashing LED H-S81-HS Installation & Operation Manual — Form Number XX-XXXX—X P/N LS10114-000HI-E:A 2/24/2015...
  • Page 65: Configuration

    Should 500 mA per line not be enough, it is possible to connect the optional module S81-T8008-1 to module S81-F5003-1. The former will add 4 x 2A at 24 VDC polarity reversal outputs. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 66: Standard Connection Diagrams

    Gray/Pink Output 6 ∅ Red/Blue S81/CCT1 ∅ White/Green Output 7 S81-T8001-1 ∅ Brown/Green ∅ White/Yellow Output 8 ∅ Yellow/Brown Figure 2.30 Field Connections Standard Connection Diagrams Figure 2.31 Standard Connection Diagram H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 67: 8: S81-F5004-1 & S81-F5004-2

    Output status in case of CPU fault Frozen in the last status / Off Enable/Disable status export to Hosts No, TCP1, TCP2, RS232 Enable/Disable commands from Hosts No, TCP1, TCP2, RS232 on the channel H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 68: Field Connections

    NOTE: The module can control resistive or inductive loads with a maximum current of 2A. Should the module be used for controlling filament lamps, the maximum load power shall not exceed 10W. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 69: 9: S81-F6001-1

    Main secondary discharge Reserve secondary discharge Intermittent audible indications Continuous audible indications Manual activation Automatic activation Automatic exclusion Emergency hold Release inhibition Reserve bank Secondary discharge Triggered system General trouble General disable H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 70: Configuration

    Reset inhibit time 1-30 minutes Hold operating mode Mode-A / Mode-B Field Connections This module does not feature any field connections, and therefore requires no terminations. Figure 2.34 Fire Extinguishing System H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 71: 10: S81-F6002-1

    NOTE: Logic function virtual inputs are set in output zones, whereas logic function virtual outputs are set in zone sensors. Logic Functions The following time diagrams describe in detail the operation of the various logic functions of the module. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 72 Parts of the H-S81-HS System I/O modules  S-R Flip Flop Function  Toggle Function  Timer Function (Mode-A) H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 73: Field Connections

    TX Pol. (Green LED) It lights up every time data are transmitted from the module to loop devices. RX Pol. (Green LED) It lights up every time data from loop devices are received H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 74: Configuration

    The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type.  S81-E2001-1 Bus The module is connected to a S81-T8003-1 termination module with 8 terminals with a 20-way flat cable. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 75 +Loop Output White ∅ -Loop Output Brown ∅ +Loop Input Green ∅ -Loop Input Yellow ∅ ∅ ∅ S81/CCT4 ∅ S81-T8003-1 Figure 2.35 Field Connections Figure 2.36 Loop standard connection diagram H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 76: Description

    • Supply voltage: 22-29VDC • Quiescent current: 70mA • Operating temperature: -5 - 50 °C • Storage temperature: -30 - 80 °C • Maximum humidity: 95% (RH) non-condensing • Hot swap capability: H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 77: Configuration

    0-500 0-500 0-999 ppm 0-999 0-999 0-100%LEL 0-100 0-100 0-25%O2 0.0-25.0 0.0-25.0 15-25%O2 15.0-25.0 15.0-25.0 4-20 mA 4.0-20.0 4.0-20.0 0-100 °C 0-100 0-100 0-150 °C 0-150 0-150 0-10 V 0.0-10.0 0.0-10.0 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 78: Field Connections

    -Loop Output Brown ∅ +Loop Input Green ∅ -Loop Input Yellow ∅ ∅ ∅ S81/CCT4 ∅ S81-T8003-1 Figure 2.37 Field Connections Standard Connection Diagrams Figure 2.38 Standard Connection Diagram of Technological Controls H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 79: Technical Features

    TX Pol. (Green LED) It lights up every time data are transmitted from the module to loop devices. RX Pol. (Green LED) It lights up every time data from loop devices are received H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 80: Configuration

    Termination with Flat Cable Termination with Multi-conductor Cable ∅ +Loop Output White ∅ -Loop Output Brown ∅ +Loop Input Green ∅ -Loop Input Yellow ∅ ∅ ∅ S81/CCT4 S81-T8003-1 ∅ Figure 2.39 Field Connections H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 81: Standard Connection Diagrams

    Marine Din Rail Switch Monitor Plus X-SMP Powered by the loop 55000-181MAR Marine Din Rail Sounder Control Unit X-SCU Requires external power supply 58000-600MAR Discovery Marine Optical smoke detector D-OSD Powered by the loop H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 82: Technical Features

    TX Pol. (Green LED) It lights up every time data are transmitted from the module to loop devices. RX Pol. (Green LED) It lights up every time data from loop devices are received H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 83 The module is connected to a S81-T8003-1 termination module with 8 termi- nals with a 20-way flat cable.  S81-E2001-2 Bus The module is connected to the field terminal block with the S81-CCT4 4-conductor multi-polar cable. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 84 Module for 4-20mA analog interface with 1 channel TEC2 IIG4N Module for 4-20mA analog interface with 4 channels TEC2 M700KW Outdoor red alarm button with isolator PULL M700KI Red alarm button with isolator PULL H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 85 WMON3 WL-MCP Wireless alarm button WPULL WL-D100 Wireless optical smoke sensor WPHOT WL-D200 Wireless optical/rate of rise heat detector WTH58 WL-D350 Wireless 58°C heat sensor WTH58 WL-SDN Wireless electronic sounder WHORN H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 86: Technical Features

    1 to 15 seconds (only for pulsing and intermittent modes) Output type Actuators Normal / Sounder Enable/Disable status export to Hosts Sensors/Actuators No, TCP1, TCP2, RS232 Enable/Disable commands from Sensors/Actuators No, TCP1, TCP2, RS232 Hosts on the channel H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 87: Field Connections

    RS485 primary line termination added RS485 primary line termination removed Field Connections The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 88 Figure 2.43 Field Connections Standard Connection Diagrams Figure 2.44 RS232/RS485 Standard Connection Diagram NOTE: For additional details on the use of this module, please refer to the specific document ST-007-IT-R1 RTU Modbus Protocol. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 89 No, TCP1, TCP2, RS232 on the channel Field Connections The module can be connected to field terminal block by using a flat or a multi-conductor cable, depending on the used bus type. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 90 The weighing module communicates with the control module through the RS485 bus that accepts up to 32 mod- ules. Two thresholds, pre-alarm and alarm, can be set per weighing module when programming. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 91 S81-F4002-1 Module with 2 x 4-20mA analog inputs S81-T8003-1 S81-CCT7 S81-F4002-2 Module with 2 x 4-20mA analog inputs Not available S81-CCT7R S81-F4003-1 Module with 8 x 4-20mA analog inputs S81-T8003-1 S81-CCT3 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 92 S81-F3002-1, S81-F5002-1, S81- F5003-1 Technical Features • Number of terminals: • Assembly: on DIN bar • Dimensions: W 57 x H 77 x D 50 mm H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 93: Field Connections

    +An. In 6 + Output 6 N.C. GND RS485 ∅ N.C. +An. Out 2 +An. In 7 + Output 7 N.C. N.C. ∅ N.C. N.C. +An. In 8 + Output 8 N.C. N.C. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 94: 3: S81-T8005-1

    Connect to +25V with a 200mA fuse Not used The S81-T8007-2 module can be connected directly to the S81-E2001-2 bus with cable S81-CCT1 without the need for the S81-T8005-1 interconnection module. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 95: 4: S81-T8002-1

    These 4 terminals connect Function Cable Color ∅ RX data input positive White ∅ RX data input negative Brown ∅ TX data output positive Green ∅ TX data output negative Yellow H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 96: 5: S81-T8004-1

    Supply voltage ground fault (earth leakage) check disabled WARNING: EARTH GROUND THE SUPPLY VOLTAGE OF THE H-S81-HS CONTROL PANEL IS NOT REFERENCED TO EARTH. IN SOME DEVICES, SUCH AS PERSONAL COMPUTERS, THE POWER SUPPLY NEGATIVE IS EARTHED FOR SAFETY REASONS. WHEN THESE DEVICES ARE CONNECTED TO THE CONTROL PANEL, A GROUND FAULT (EARTH LEAKAGE) TROUBLE IS SIGNALED.
  • Page 97: Internal Connections

    Safety ∅ Disabling Normally de-energized ∅ External buzzer Normally de-energized ∅ Normally de-energized ∅ Alarm Normally energized ∅ Tampering Normally energized Security ∅ Trouble Normally energized ∅ External sounder Normally energized H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 98: Field Connections

    EN-54-2 COMPLIANCE THE REMOTE EVACUATION CONTROL AND REMOTE CONTROL PANEL RESET INPUTS MUST NOT BE ACTUATED DIRECTLY THROUGH EXTERNAL MANUAL BUTTONS SINCE THEY ARE NOT MONITORED. THIS GUARANTEES COMPLIANCE WITH STANDARD EN-54-2. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 99: Standard Connection Diagrams

    W 135 x H 77 x D 50 mm Status Indications The module includes 8 green LEDs for relay status indication: Condition LED1 - LED8 (Green LEDs) It lights up when relay coil is active H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 100: Field Connections

    W 170 x H 77 x D 50 mm Status Indications The module includes 16 green LEDs for relay status indication: Condition LED1 - LED16 (Green LEDs) It lights up when relay coil is active H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 101: Field Connections

    LED1 - LED4 (Green LEDs) They light up when outputs are active Internal Connections  BR1 Terminal Block 2-way terminal block for power supply connection. Function Notes ∅ 25VDC power supply positive ∅ 25VDC power supply negative Black H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 102: Field Connections

    - Output 2 Maximum current 2A ∅ + Output 3 ∅ - Output 3 ∅ + Output 4 ∅ - Output 4 Standard Connection Diagrams Figure 2.49 Sounder Standard Connection Diagram H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 103: Blank Panels

    They close empty module slots in the rack. 2.6.1 Description This is a series of front panels used to close empty module slots on I/O racks and on the central unit rack. Figure 2.50 Blank Panels H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 104: Cables

    S81-F7008-1 Control module for scales S81-T8003-1 S81-CCT6 S81-F7009-1 Loop module with XP95/Discovery protocol S81-T8003-1 S81-CCT4 S81-F7010-1 Loop module with System Sensor protocol S81-T8003-1 S81-CCT4 1 Combined with the S81-T8001-1 termination module H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 105: Section 3: Installation

    NOTE: All the parts used in H-S81-HS systems are selected depending on the relevant intended use and are suitable for operating in compliance with the technical specifications and the relevant environmental conditions therein specified.
  • Page 106: Positioning The H-S81-Hs-1/10R Control Panel

    The control panel must be located in an easily accessible place, well signaled and protected against fire. Place the cabinet on a dead level floor after providing a suitable housing for cable entry. Figure 3.3 Ground-floor Steelwork H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 107: Layout Of H-S81-Hs/1R Internal Parts

    Installation 3.5 Layout of H-S81-HS/1R Internal Parts The picture below shows the typical layout of the parts located on the base plate of H-S81-HS/1R type control panels. In this specific configuration, field device cables are connected to I/O modules with termination modules or multi-conductor cables. Light blue cable trays are only for cables con- necting I/O racks to termination modules.
  • Page 108: Layout Of H-S81-Hs/2R Internal Parts

    Layout of H-S81-HS/2R Internal Parts 3.6 Layout of H-S81-HS/2R Internal Parts The picture below shows the typical layout of the parts located on the base plate of H-S81-HS/2R type control panels. In this specific configuration, field device cables are connected to I/O modules with termination modules or multi-conductor cables.
  • Page 109: Layout Of H-S81-Hs/1-10R Internal Parts

    For the entry of the main supply cable, use the proper cable connector on the right side of the pre-drilled plate. Use only cable connectors with V1 or higher flammability rating. NOTE: H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 110: Earth Grounding Instructions

    There must be a secondary power source (battery) to power the system in case of primary mains supply failure. The H-S81-HS control panel can charge two 12V sealed lead batteries connected together in series, with a maximum capacity of 120 Ah. Refer to the spreadsheet of the paragraph to...
  • Page 111: 1: Replacement Of Battery Fuses

    For this type of signal we recommend using shielded twisted cables CEI EN 50200 3 x 1.5 mm . In this case, please take utmost care when selecting the conductors to avoid that the voltage drop along the cable may prevent the connected devices from operating. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 112: 3: Addressable Loop Cables

    CEI EN 50200. Also in this case, check the voltage drop on the cable and increase its section, if necessary. NOTE: Use the relay contacts on S81-T8006 and S81-T8007 relay termination modules only with Safety Extra Low Voltages. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 113: Start-Up

    Disconnect the shield from the shield bar and make sure it is insulated from the earth. Make sure that there is no short circuit between terminals +Lout and -Lout. Make sure that there is no short circuit between terminals +Lin and -Lin. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 114: 5: Functional Tests

    All outputs are tested in all of the statuses defined by the application program. All program logical paths are tested. All preset delays are checked. All combinations of digital signal permutations are checked - fault conditions included. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 115: 3: I/O Module Fault

    Start-Up and Fault Management 4.2 Management of Faults This paragraph describes the behavior of system H-S81-HS when the various faults occur. 4.2.1 Power Supply Set Fault The fault of the power supply set is detected by the central unit during operation. Fault type and details are shown on the display.
  • Page 116: 6: Battery Replacement

    Remove the new module from the package taking care not to touch the electronic components. Insert the new module firmly and tighten the two fixing screws on the front panel. Wait for some seconds until the fault indication disappears from the display. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 117: Replacement Of Fuses

    Honeywell for repair, together with a brief description of the type of fault. 4.2.11 Customer Service and Training The customer service of Honeywell can support the final user during design, development and test- ing of H-S81-HS-type systems. Furthermore, specific training courses on this product can be orga- nized on request at our premises.
  • Page 118: Section 5: Maintenance

    System and equipment maintenance must be carried out by skilled staff at regular intervals. 5.1 Steelwork The steelwork of the H-S81-HS control panel does not require special maintenance. However, we recommend cleaning and/or replacing the air intake filters located on the cabinet side walls at regu- lar intervals and, moreover, periodically checking that the terminals connecting the cables from field devices are properly tightened.
  • Page 119 FUNCTIONAL TESTS MUST BE CARRIED OUT BY A SKILLED TECHNICIAN, UNDERTAKING THE PROPER SAFETY MEASURES SO TO AVOID ACCIDENTAL DISCHARGES OF THE EXTINGUISHING AGENT OR THE ACTIVATION OF OUTPUTS THAT MAY BE HARMFUL TO THE ENVIRONMENT OR PEOPLE. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 120: Section 6: Application Notes

    • S81-F5003: 8 output module for visual and audible alarm device control and monitoring • S81-F5002: 16-relay output module for controlling blockages, replications, etc. • S81-F6001: Module gathering the visual signals of one extinguishing zone H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 121: 2: Compulsory Functions

    H-S81-HS/1-10R 6.2.1 Processing of signals and indicators The H-S81-HS system receives and shows the signals relating to the different extinguishing zones. The central unit processes the logics. The information is sent to the display unit. Both compulsory and optional functions are carried out by the modules as described in Sections 6.2.2 and 6.2.3.
  • Page 122: 4: Light Indicators

    Outputs for visual and audible alarm device control (TOA) 6.2.7 Non-monitored Outputs S81-F5002 type modules, combined with the termination module S81-T8007, can monitor the out- puts controlling equipment external to the system (door release, ventilation stop, etc.) H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 123: Activated" Condition

    If the “released” condition is activated further to the receipt of the signal relating to extinguishing agent flow without the d.e.c. being in the “Activated” condition (Manual release by mechanical command) the local sounder is also activated. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 124: Resetting The "Activated" And "Released" Conditions

    The system features inputs for receiving the signal that represents extinguishing agent flow (PSH). If this signal is received without the “Activated” condition, the “Released” condition activates. Therefore, all relevant outputs will be activated. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 125: Mode-A

    The system can control equipment located inside the fire extinguishing zone. E.g. Pilot cylinders, visual alarm devices, etc. The modules to be used for these purposes are: • S81-F5003: for controlling visual and audible alarm devices • S81-F5001, S81-F5004: for controlling solenoids, valves, etc. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 126: Releasing Signals To The Reserve Cylinders

    • If one of the two modules is faulty, the other one will become effective for logic processing. Therefore, logics on redundant channels shall always be OR, and never AND. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 127: 1: I/O Module Redundancy

    Therefore, redundancy in this document refers to I/O modules only, and not to field devices. With respect to this, we would remind that complete redundancy (modules + field devices) is possi- ble for all I/O modules without restrictions. The I/O modules of the H-S81-HS system can be divided into two categories: •...
  • Page 128: Operator Interface

    Setting date and time • Configuring control panel parameters 7.1 Operator Interface The operator interface of the H-S81-HS control panel includes: a graphic display, 14 indicator LEDs, and a 23-key keyboard. Figure 7.1 Operator Interface 7.1.1 Visual Indicators ALARM LED (fire alarm function) It flashes when an alarm status is received from one input defined as fire when programming.
  • Page 129: Buttons

    1. The display shows a message informing that reset has been completed, which is stored in the event history and sent to any peripheral devices (host/printer). This function can be activated only after silencing local buzzer and sounders. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 130 It allows to access directly the menu of the access level active when it is pressed 1/9 number keys (fire/burglar alarm function) They are used to select password digits and to enter new data in the menus of the operator cycle H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 131: Fire Alarm Section Menu (Safety)

    Figure 7.2 Structure of the Fire Alarm Section Menu 7.3 Access to Functions There are four different access levels for the fire alarm section. • Level 1: accessible to the PUBLIC • Level 2: accessible to the USER H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 132: Operations At Access Level 1

    Figure 7.3 Standby Mode 7.4.1 Local Buzzer Silencing Press the button Local Buzzer Silencing. The last line of the display will show a confirmation mes- sage for two seconds. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 133: 2: Delay Override

    Go to the central line using the arrow buttons and use the Scroll to view the chronological sequence of the alarmed zones. For viewing the list of alarmed devices, go to the relevant zone and press Enter. Figure 7.5 Details of Zones with Active Fire Alarms H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 134: Overview Of Zones With Active Fire Pre-Alarms

    During this stage, any new events having higher priority will be immediately shown on the display. The presence of events with lower priority will be signaled as shown in the picture below. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 135: View

    To view the list of disabled zones and devices. 7.5.3 Event History To view the history of the last 250 events. The following information is shown for each event: • Progressive number • Date and time of occurrence H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 136: 4: Alarm History

    Figure 7.10 Main Menu at Access Level 2 The control panel will automatically exit the selected access level after an idle time of one minute. The following operations are allowed at access level 2: H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 137: 1: Sounder Silencing

    Select this option to enable/disable all the sensors of one zone. 7.7.2 Whole Actuator Zone Select this option to enable/disable all the actuators of one zone. 7.7.3 Individual Devices Select this option to enable/disable a single sensor or actuator. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 138: 4: Local Sounder

    By selecting this option, the system date/time setting page is displayed. This step allows to change the various parameters. If the entered value is not allowed, an error message is displayed. Figure 7.13 Changing Date/time H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 139: Zone Test

    The zone test mode is automatically exited after 2 hours, or by manually disabling the zone test from the same menu. During the test, the main page displays the remaining time. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 140: Configuration

    In case of S81-F4002 or S81-F4003 type modules, first of all enter the number of the chan- nel whose thresholds are to be changed. Then, the screen below will be displayed: H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 141: Fire Extinguishing Modules

    C, the Hold condition interrupts the discharge delay time count 10 seconds before it is over. Parameters can be changed by using the arrow buttons as fol- lows: H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 142: Printer

    Below are the allowed field values and their meaning: Printer Selection of printer type • Disab.: Serial printer disabled. • 40 col.: Serial printer enabled for 40 column printing. • 80 col.: Serial printer enabled for 80 column printing. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 143: Host Computer

    To configure the stop bit number of the serial communication. Allowed values are: 1 and 2. Parity To configure the parity control of the serial communication. Allowed values are: No (no parity), Odd (off parity) and Even (even parity). H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 144: Tcp-Ip

    To define the range of a host in an IP network in order to reduce network traffic and simplify the research of a certain IP address. NOTE: Values 127.000.000.001 and 000.000.000.000 mean that the relevant function is disabled. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 145: 4: Standard Options

    Mode the internal sounder is activated in case of fire alarm or further to the evacuation command. By selecting the Buzzer Mode the sounder is activated simultaneously to the local Buzzer. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 146: 5: Change Password

    The main CPU sends the configuration parameters of all programmed devices to each module. Module Enable The main CPU enables module operation. Clock Synchronization The main CPU synchronizes system clock to check time slot status. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 147: 1: Disabled Condition

    The General Disable LED lights up steadily. • The Device Disable LED lights up steadily. • The Sounder Disable LED lights up steadily. (Only if the output type is Sounder) The General Disable relay activates. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 148: 2: Trouble Condition

    The Sounder Trouble LED flashes (only if the trouble affects a Sounder type output). The General Trouble and/or System Trouble relays deactivate, according to the type of trouble. Figure 7.27 Trouble Condition Press Esc to view the details of the trouble. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 149: Fire Pre-Alarm Condition

    • The local sounder activates. • The Alarm LED flashes. • The Fire Alarm relay activates. Figure 7.29 Fire Alarm Condition Press Esc to view the details of the fire alarm. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 150: 5: Supervisory Condition

    In case of gas alarm condition, the control panel carries out the following operations: • The intermittent local buzzer activates. • The Gas Alarm relay activates. Figure 7.31 Gas Alarm Condition Press Esc to view the details of the gas alarm. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 151: Burglar Alarm Section (Security)

    Level 2 or 3 require the relevant passwords. Control panels are supplied with the fol- lowing default passwords that can be changed in the operator cycle: Access level Prefix Password Burglar alarm Level 2 (Area-2) 22213 Burglar alarm Level 3 (Area-2) 74512 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 152: Operations At Access Level 1

     Access to Configuration menu The burglar alarm section of the H-S81-HS control panel complies with IMQ first level. The func- tions for viewing and controlling this section do not interfere with those of the fire alarm section, which have higher priority.
  • Page 153: Exclude/Include

    Figure 7.35 View 7.17.1 Configured Zones For viewing the complete list of the programmed zone in area 2. The complete list of sensors and actuators can be viewed for each selected zone. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 154: 2: Zone Status

    By entering level 3 password, preceded by the prefix 2, the main menu shown below is accessed. Figure 7.36 Main Menu at Access Level 3 The Exclusion/Inclusion and View options are the same as those of level 2. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 155: Disable/Enable

    This function is used, for instance, for monitoring a sensor. NOTE: Only 10 devices can be tested at the same time. The test mode can be manually removed from the same menu. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 156: Configuration

    7.21.1 Time Slots This option sets the validity periods for 10 intervals of the 10 time slot categories. First of all, select the category number and desired interval: Figure 7.39 Time Slots H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 157: Holidays

    This options sets the holiday periods valid for 10 intervals of the 10 time slot categories. First of all, select the month where to add or remove a holiday: Figure 7.41 Holidays H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 158: 3: Standard Options

    This parameter sets the reset time of the default outputs of the burglar alarm section. Value ranging between 1 and 10 minutes. NOTE: This time must be kept >/3 minutes in order to comply with IMQ level 2. H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 159: 4: Change Password

    CPUs, the other one will keep operating without any interruptions. The faulty CPU is indicated on the display of system fault list. CPU hot swapping is allowed (hot plug). Figure 7.44 CPU Redundancy H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 160: Appendix A: Parts List

    Appendix A: Parts List The tables below list the modules, expansion modules and devices making up the H-S81-HS sys- tem, sorted by product type. A.1 Steelwork Part Number Description Notes S81-CB001 Single rack control panel steelwork (wall installation) H700mm, W600mm, D400mm...
  • Page 161: A.3: Central Unit Rack

    Control module for Honeywell bus Redundancy not possible S81-F7008-1 Control module for scales Redundancy not possible S81-F7009-1 Control module for Apollo bus Redundancy not possible S81-F7010-1 Control module for System Sensor bus Redundancy not possible H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 162: A.6: Termination Modules

    14-way flat cable 2 meters S81-CFT20/05 20-way flat cable 5 centimeters S81-CFT20/2 20-way flat cable 2 meters S81-CVSC4 8-way RJ cable 19cm S81-CVSC5 8-way RJ cable 36cm S81-CVSC12 8-way RJ cable 60cm H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 163: Appendix B: Compatible Devices

    Appendix B: Compatible Devices The tables below list the field devices compatible with H-S81-HS control panel, sorted by product type. B.1 Hochiki Conventional Detectors Part Number Description Notes SLR-E3N Smoke detector DCD-AE3 60° combined heat detector DFJ-AE3 60°C fixed temperature heat detector...
  • Page 164: B.3: Honeywell Addressable Devices

    55000-812 Din Rail Zone Monitor 55000-182 Din Rail Sounder Control Unit 55000-773MAR Marine Din Rail Zone Monitor 55000-772MAR Marine Din Rail Switch Monitor Plus 55000-181MAR Marine Din Rail Sounder Control Unit H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 165 Discovery Manual call Point Red 58100-950 Discovery W.P. Manual call Point Red 45681-393 Discovery Sounder/Beacon Base 58000-005 Discovery Open Area Sounder/Beacon 55000-295 Intelligent Dual IR Flame detector ATEX 55000-021 Intelligent Triple IR Flame detector ATEX H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 166: B.5: System Sensor Addressable Devices

    Combined wireless optical/rate of rise heat detector WL-D350 Wireless 58° C heat sensor WL-SDN Wireless wall sounder with 3 selectable tones WL-STR Wireless red beacon WL-SS Wireless sounder + beacon WL-IND Wireless remote alarm repeater H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 167: B.6: Visual And Audible Alarm Devices

    Visual and Audible Alarm Devices Compatible Devices B.6 Visual and Audible Alarm Devices Part Number Description Notes To be used with S81-F5003-1 modules H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 168: Appendix C: Power Supply Set Dimensions

    90°C fixed temperature heat detector 0.00004A 0.04000A DRD-E IR flame detector 0.00007A 0.04000A NO contact Normally open contact 0.00400A 0.02600A NC contact Normally closed contact 0.02600A 0.00400A Total standby current (A2) Alarmed (B2) H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 169: C.3: Absorption Of Hochiki Addressable Devices

    Module with 1 x 0-10V input 0.00025A 0.01000A S81-Mod-DO Module with 8 open collector outputs 0.00025A 0.01000A S81-Mod-DISP 255 message display module 0.03000A 0.05000A Total standby current (A4) Alarmed (B4) (A) both channels alarmed H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 170: C.5: Absorption Of Apollo Addressable Devices

    Discovery Sounder/Beacon Base 0.00035A 58000-005 Discovery Open Area Sounder/Beacon 0.00035A 55000-295 Intelligent Dual IR Flame detector ATEX 55000-021 Intelligent Triple IR Flame detector ATEX 0.00220A 0.0042A Total standby current (A5) Alarmed (B5) H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 171: C.6: Absorption Of System Sensor Addressable Devices

    FDX551REM Rate of rise heat detector 0.00015A 0.0050A FDX-551HTE 78° heat sensor 0.00015A 0.0050A FDX-751-TEMI Optical/rate of rise heat detector IDX751AE Intrinsically safe optical sensor Total quiescent current (A6) Alarmed (B6) H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 172: C.7: External Load Absorption

    NOTE: Use the suitable power supply set according to the total current calculated with alarmed system. C.9 Calculation of Battery Capacity According to the European and US standards, the operating time of H-S81-HS control panel with primary voltage failure is: •...
  • Page 173 The table below shows the lead battery type to be used according to the calculated capacity Part Number Description 6FM40-X 12 V - 40 Ah batteries 6FM65-X 12 V - 65 Ah batteries 6FM120-X 12 V - 120 Ah batteries H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 174: Appendix D: Adhesive Labels

    Appendix D: Adhesive Labels D.1 CPR Adhesive Label H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 175 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015...
  • Page 176 Honeywell International Inc. Industrial Fire Protection 12 Clintonville Road Northford, CT 06472-1610 Honeywell Industrial Training Center +1 203-484-7161 9401 Bay Area Boulevard #400 fax: +1 203-484-7118 Pasadena, TX 77507 LS10113-000HI-E 2/24/15 www.honeywell.com +1 713-577-1510 © 2015 Honeywell International Inc.