2: Edit Voice Commands - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

Network Management
Control Lockout
The Control Lockout countdown timer is set to the programmed value when an LOC gains EVS Control. The timer starts over upon any key
press at the EVS Control LOC. While the Control Lockout timer is active, an LOC of equal priority must request EVS control. The Control
Lockout timer is cleared when EVS Control is relinquished. The Control Lockout timer does not apply to EVS Super User control.
Select Immediate/Timer/Never
Range 0-720 min/0-59 sec
Auto Reset EVS MIC Triggered Event
If the Timer is selected, the event will automatically reset after being active for the programmed time. If Event Disabled is selected, the event
will not be allowed to be activate from an LOC Station. Selecting Never will require an emergency system reset to be performed to reset the
event.
Select Never/Timer/Event Disabled, Range from 1-240 min
6.3.2 Edit Voice Commands
When a voice output group is selected to be activated by a zone, the cadence pattern choice does not apply. For voice output groups, one of
six system wide voice commands will activate instead of the cadence pattern.
1.
Login to the panel. The panel will automatically access the Main Menu.
2.
Select 6 for Network Programming Menu.
3.
Select 7 for Voice Options.
4.
Choose Site.
5.
Select 2 for Edit Voice Commands.
6.
Select the command you wish to edit:
• Fire Alarm
• Fire System Aux 1
• Fire System Aux 2
• Fire Zone Aux 1
• Fire Zone Aux 2
• Fire Prealarm
• Emergency Communication 1
• Emergency Communication 2
• Emergency Communication 3
• Emergency Communication 4
• Emergency Communication 5
• Emergency Communication 6
• Emergency Communication 7
• Emergency Communication 8
• Fire Supervisory
• System Alert 1-5
• Trouble
• Fire Interlock Release
• Fire Interlock Alert
• Custom Emergency Comm
• Emergency Supervisory
• CO Alarm
• CO Supervisory
7.
Select whether a Message or Tone Only should be played. If Message is selected, choose the desired message for the command.
70
EVS Timer
Control Lockout
Auto Reset EVS MIC Triggered Event
Auto Reset EVS Event 1
Auto Reset EVS Event 2
Auto Reset EVS Event 3
Auto Reset EVS Event 4
Auto Reset EVS Event 5
Auto Reset EVS Event 6
Auto Reset EVS Event 7
Auto Reset EVS Event 8
Table 6.1 Auto Reset EVS MIC Triggered Event Timer Menu
Option
Immediate/Timer/Never
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
Never/Timer/Event Disabled
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Voice Options

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820evs

Table of Contents