Sia - Panel Communicator - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

Reporting
11.3 SIA – Panel Communicator
(Differences/additional features are underlined)
Events are sent to the Central Station Receiver as a fixed length string:
The event format is:
EEPPMMZZZZ
Where
EE
Event code (2 characters)
PP
Panel number (2 digits – Zero Filled) (valid range from 1 to 64)
MM
Module number (2 digits – Zero Filled) (valid range from 1 to 98, typically
Module information)
ZZZZ Event parameter (4 digits – Zero Filled) (typically Point, Zone or Circuit
information)
1.
The Event field will contain 10 digits including the 2 digit event code (EE), 2 digit panel ID (PP), 2 digit Module Number (MM) and a
4 digit Event Parameter (ZZZZ).
2.
Based on the actual Event Code, the Module Number or Event Parameter fields might not contain pertinent information. In that case the
field will contain zeros.
3.
The account number is sent using an account block that is separate from the event block.
4.
Multiple events can be sent within a single event block. Events are separated by a "/" character.
5.
Event parameter can be a Zone, Point or Circuit Number.
6.
"pi" modifier event is not used.
7.
Panel can be set to report by either Point or Zone.
For examples see Table 11.4 below.
Fire Alarm-Zone
Fire Alarm-Zone
Fire Alarm-Point
Fire Alarm-Point
Expander Trouble
Auto Test
Battery Trouble-Panel 32
Battery Trouble-Expander 18
SLC Loop Shorted
Program Begin
Program Begin
AC Power Loss- Panel 22
Fire Trouble
Fire Trouble
Fire Trouble-NAC
Fire Trouble-NAC
148
Report
Panel ID
Event
Zone/
Point
Zone
32
Zone
32
Point
32
Point
21
n/a
15
n/a
32
n/a
32
n/a
32
n/a
01
n/a
32
n/a
22
n/a
22
Point
22
Zone
22
Point
22
Zone
22
Table 11.4 SIA Reporting Examples
Module
Zone
Point
PP
MM
ZZZZ
ZZZZ
n/a
15
n/a
n/a
05
n/a
01
n/a
123
33
n/a
203
11
n/a
n/a
n/a
n/a
n/a
98
n/a
n/a
18
n/a
n/a
44
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
98
n/a
n/a
97
n/a
200
97
1
n/a
98
n/a
NAC Circuit 7 EE-PP-MM-ZZZZ FT22980007
98
n/a
NAC Circuit 7 EE-PP-MM-ZZZZ FT22980007
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
SIA – Panel Communicator
Fields
SIA Event
Sent
Data
EE-PP-MM-ZZZZ FA32000015
EE-PP-MM-ZZZZ FA32000005
EE-PP-MM-ZZZZ FA32010123
EE-PP-MM-ZZZZ FA21330203
EE-PP-MM-ZZZZ ET15110000
EE-PP-MM-ZZZZ RP32000000
EE-PP-MM-ZZZZ YT32980000
EE-PP-MM-ZZZZ YT32180000
EE-PP-MM-ZZZZ ET01440000
EE-PP-MM-ZZZZ LB32000000
EE-PP-MM-ZZZZ LB22000000
EE-PP-MM-ZZZZ AT22980000
MM = 00
EE-PP-MM-ZZZZ FT22970200
EE-PP-MM-ZZZZ FT22970001
MM = 00
ZZZZ=Pt. #
ZZZZ=OPG #

Advertisement

Table of Contents
loading

This manual is also suitable for:

6820evs

Table of Contents