Section 8: Programming; Ul 864 / Ul 2572 Programming Requirements; Modules; 1: Edit Modules - Honeywell 6820 Manual

Addressable fire alarm conrol panel
Table of Contents

Advertisement

This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses
these menu options in detail. All options described in this section can be performed using the HFSS Honeywell Fire Software Suite.
NOTE: JumpStart auto-programming should be run Before any customized programming is performed. Thoroughly test the system after
running JumpStart because it automatically programs the system, searching for and configuring all SLC and SBUS devices it finds. JumpStart
allows you to confirm the integrity of the installation prior to performing any custom programming. After determining that the hardware is properly
installed, custom programming can be performed.

8.1 UL 864 / UL 2572 Programming Requirements

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES:
This product incorporates field programmable software. In order for the product to comply with the requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864 and UL 2572, certain programming features or options must be limited to
Programming Option
Time Options
Time Options
Communication Options
Silencing Options
Display Oldest Event
Initial Delay
1
Alarm Verification
2
Manual Release Switch
Auto Reset
EVS MIC Triggered Event
EVS Input
Event Priority
1
When 2-count delay is active, you cannot use the alarm verification.
2
The Manual Release Switch shall override any pre-discharge delays resulting in an immediate release or start of the Manual Release Delay
period. The delay period shall be 30 seconds or less from the activation of the switch to the actuation of the releasing device(s).
3 Temporal 4 and other recognized coding should not be used for NAC circuits mapped to CO supervisory events.

8.2 Modules

This section lists the options available under the module option in the Panel Programming. The following modules are available for the con-
trol panel: 5824 serial/parallel/IO printer interface module, 6860, 5860, and 6855 LCD remote annunciators, 5815XL SLC Loop expander
for SD devices, 6815 SLC Loop Expander for devices, 5895XL power supply,5496 NAC expander, 5880 LED I/O module, 5865 LED
annunciator Module, EVS-50W, EVS-125W, EVS-INT50W, EVS-100W audio amplifiers, EVS-VCM voice control module, EVS-RVM
remote voice module, and SK-NIC network interface card.
8.2.1 Edit Modules
The features that can be edited when this option is selected are module ID, module name, or features that are specific to the module to be
edited.
To edit an existing module:
1.
Login to the panel. The panel will automatically go to the main menu.
2.
Select 7 for Panel Programming.
3.
Press 1 to enter Module Menu.
4.
Press 1 to edit a module.
5.
Use the up or down arrow key to select the module you wish to edit.Then press ENTER.
90

Section 8: Programming

specific values or not used at all as indicated below.
Permitted
Menu Item
in UL 864
(Y/N)
Auto-resound
Yes
Low AC Report Delay Yes
Auto Test Time
Yes
Auto Silence
Yes
Y (Enabled)
Yes
N (Disabled)
No
0-28
Yes
Alarm Verification
Yes
Manual Release
Yes
Auto Reset EVS MIC
Yes
Triggered Event
EVS Input
Yes
CO Alarm
No
Table 8.1 Programming Requirements
Permitted
in UL 2572
Possible Settings
(Y/N)
Yes
4 hrs, 24hrs
Yes
0-30 hours
Yes
4, 6, 12, and 24 hrs
Yes
0-60 minutes
Yes
Yes or No
No
Yes or No
Yes
0-28 hours
Yes
60-250 seconds
(Confirmation
period)
Yes
0-120 seconds
(delay period)
Yes
Never
Timer Event
Disabled
Yes
Latching
Non-Latching
No
Yes & No
6820/EVS Manual — P/N LS10144-001SK-E:E 4/6/2022
Settings Permitted
Settings Permitted in
in UL 864
4 hours if using
4 hours if using
SWIFT devices
SWIFT devices
24 hours if using
24 hours if using other
other devices
devices
1-3 hours
1-3 hours
4 or 6 hours
4 or 6 hours
3-60 minutes
3-60 minutes
Yes
Yes
No
No
3 hours
3 hours
0-60 seconds
0-60 seconds
0-30 seconds
0-30 seconds
(delay period)
(delay period)
Never
Never
Timer Event
Timer Event
Disabled
Disabled
Latching
Latching
No
No
UL 2572