Parameter List; Table 7: Level Transducer Block Parameters - Honeywell SLG 700 Option Manual

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Parameter List

Note: To configure level transducer block parameters from the advanced display, keep both level
transducer block and auxiliary transducer block in OOS mode. More details of the parameters can be
found in 34-SL-25-11.
Parameter
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
BLOCK_ERR
UPDATE_EVT
BLOCK_ALM
SENSOR_RANGE
PRODUCT_LEVEL
PRODUCT_LEVEL_RANGE
DISTANCE_TO_PRODUCT
PRODUCT_LEVEL_RATE
PRODUCT_LEVEL_RATE_RAN
GE
Rev.5

Table 7: Level Transducer block parameters

The revision level of the static data associated with the function
block.
The user description of the application of the block.
Used to identify grouping of blocks.
The identification number of the plant unit.
The actual, target, permitted, and normal modes of the block.
Reflects the error status associated with the hardware or software
components associated with a block. It is a bit string, so that
multiple errors may be shown.
This alert is generated by any change to the static data.
The BLOCK_ALM is used for all configuration, hardware, and
connection failure or system problems in the block. The cause of
the alert is entered in the subcode field. The first alert to become
active sets the Active status in the Status attribute. After the
Unreported status is cleared by the alert reporting task, another
block alert may be reported without clearing the Active status, if the
subcode has changed.
Display range supported by Level Sensor
Displays product level
The product level range is the user desired valid range for the level
which is limited by the maximum product height value.It also
contains the units for Product level, which Is used by all the
derived parameters. The supported units are:
m
cm
mm
in
ft
The distance measured from sensor to the top level of the product.
The Rate of change of level.
The Rate of change of level is limited by -250 m/s to +250 m/s. It
also contains unit for Prodcut Level Rate. The supported units are:
ft/s
m/s
in/min
m/h
ft/min
in/s
FOUNDATION Fieldbus Option User's Manual
Description
Page 27