OFFSPEC_ALARMS
Indicates if the device is operating outside its specified range or internal diagnostics indicates
deviations from measured or set values due to internal problems in the device or process
characteristics.
OFFSPEC_MAPPED parameter contains a list of informative conditions that do not have a
direct impact on the device's primary functions. Following are the OFFSPEC_MAPPED
conditions:
Low Supply Voltage
High Supply Voltage
PV out of Range
Comm. Board Over Temperature
Sensor Over Temperature
Surface Blocking Distance High
Surface Blocking Distance Low
Interface Blocking Distance high
Interface Blocking Distance low
OFFSPEC_MASK parameter masks any of the failed conditions listed in
OFFSPEC_MAPPED. A bit on means the condition is masked out from alarming and is
not reported.
OFFSPEC_PRI parameter designates the alarming priority of the OFFSPEC_ALM. The
default is 0.
OFFSPEC_ACTIVE parameter displays the offspec alarms that are active.
OFFSPEC_ALM parameter indicates offspec alarms. These conditions do not have a direct
impact on the process or device integrity.
If connect R101 sensor with R102 FF comm then for two liquid flooded application host side user can
observe only surface blocking distance high/low alarm even if interface blocking distance high/low
alarms generated.
Page 20
FOUNDATION Fieldbus Option User's Manual
Rev.5