Honeywell SLG 700 Option Manual page 65

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Parameter Name
LINEARIZATION
LINEARIZATION_TABLE_SIZE
CORRECTED_LEVEL1
CORRECTED_LEVEL2
MEASURED_LEVEL1
MEASURED_LEVEL2
Rev.5
An option to enable/disable the usage pf Linearization
table, When the Linearization Table is under
modification, this option should be selected as Disabled.
After updating the Linearization Table Size, Measured
Level and Corrected Level the Linearization option
should be enabled. If all the entries mentioned above are
valid then user is allowed to select the Enable option,
otherwise it will throw the Parameter Check Error
The number of levels user wants to linearize can be
updated here. This should match with the number of
entries in the Linearization table. It should not be zero
and maximum value is 32
This is the first half part of the Corrected Level
Linearization Table which supports entries for 16
elements. It can be updated for Linearization type DRY
or WET Linearization table entry is limited by the
Linearization Table Size.
This is the second half part of the Corrected Level
Linearization Table which supports entries for 16
elements. It can be updated for Linearization type DRY
or WET. The Linearization table entry is limited by the
Linearization Table Size.
This is the first half part of the Measured Level Table
which supports entries for 16 elements. The user can
modify it manually when Linearization Type is Dry. If
Linearization Type is Wet, then it is allowed to
enter/correct single entry in the Linearization table at a
time using method. While executing Level Wet
Linearization Method, Measured Level cannot be edited
by user. Value of Product Level or value of Interface
Level (Measured Product Type Two Liquid Flooded) is
copied in the Measured Level Table based on the
selected Linearization Table Index. Linearization table
entry is limited by value of Linearization table Size. If the
entry exceeds linearization size, the Parameter Check
Error is triggered.
This is the second half part of the Measured Level Table
which supports entries for 16 elements. The user can
modify it manually when Linearization Type is Dry. If
Linearization Type is Wet, then it is allowed to
enter/correct single entry in the Linearization table at a
time using method. While executing Level Wet
Linearization Method, Measured Level is cannot be
edited by user. Value of Product Level or value of
Interface Level (Measured Product Type is Two Liquid
Flooded) is copied in the Measured Level table based on
the selected Linearization Table Index. Linearization
table entry is limited by value of Linearization table Size.
If entry exceeds linearization size, the Parameter Check
Error is triggered.
FOUNDATION Fieldbus Option User's Manual
Description
Page 49