Table 12: Lcd Transducer Block Parameters - Honeywell SLG 700 Option Manual

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

3.8.3. Parameters List
Parameter
ST_REV
TAG_DESC
STRATEGY
ALERT_KEY
MODE_BLK
BLOCK_ERR
UPDATE_EVT
BLOCK_ALM
DISP_SEQ_TIME
LANGUAGE
LANGUAGE_PACK
DISPLAY_TYPE
LCD_CONTRAST
DISP_FW_VER
BLOCK_TYPE
Rev.5
Table 13: LCD Transducer block parameters
The revision level of the static data associated with the function
block.
The user description of the application of the block.
Used to identify grouping of blocks.
The identification number of the plant unit.
The actual, target, permitted, and normal modes of the block.
This parameter reflects the error status associated with the
hardware or software components associated with a block. It is a bit
string, so that multiple errors may be shown.
This alert is generated by any change to the static data.
The BLOCK_ALM is used for all configuration, hardware, and
connection failure or system problems in the block. The cause of the
alert is entered in the subcode field. The first alert to become active
sets the Active status in the Status attribute. As soon as the
Unreported status is cleared by the alert reporting task, another
block alert may be reported without clearing the Active status, if the
subcode has changed.
Periodic rotation time of the display screens in seconds.
Range 3-30 sec.
Language selection for the Display. Supported Languages: English,
French, German, Spanish, Turkish, Italian,Russian, Chinese and
Japanese. Available selections are determined by the Language
Pack supported.
Type of language pack supported
Western: English, French, German, Spanish, Italian, Turkish and
Russian
East Asian: English, Chinese and Japanese.
Type of Display Connected. Possible Values: No Display
Connected, Advanced Display.
Contrast of the LCD screen can be controlled by this parameter. Its
range is 1-9.
Version Number of Display Firmware.
Block type selection for screen process variable. The BLOCK_TYPE
is present in all the eight screens: BLOCK_TYPE_1,
BLOCK_TYPE_2, BLOCK_TYPE_3, BLOCK_TYPE_4,
BLOCK_TYPE_5, BLOCK_TYPE_6, BLOCK_TYPE_7 and,
BLOCK_TYPE_8.
FOUNDATION Fieldbus Option User's Manual
Description
Page 67