Honeywell SLG 700 Option Manual page 90

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Parameter
L_TYPE
The state (Direct or Indirect) values that are passed from the transducer block to the
AI block.
When L_TYPE = Direct, the values are passed directly from the transducer block to
the AI block. (No units conversion.)
When L_TYPE = Indirect, the values from the transducer block are in different units,
and must be converted either linearly (Indirect) or in square root (Ind Sqr Root) using
the range defined by the transducer and the OUT_SCALE range.
LOW_CUT
If the percentage value of transducer input fails below this, PV = 0.
PV_FTIME
The time constant of the first-order PV filter. It is the time required for a 63% change
in the IN value.
FIELD_VAL
The value and status from the transducer block or from the simulated input when
simulation is enabled.
UPDATE_EVT
This alert is generated by any change to the static data.
BLOCK_ALM
The block alarm is used for all configuration, hardware, and connection failure or
system problems in the block. The cause of the alert is entered in the subcode field.
The first alert to become active sets the Active status in the Status parameter. As
soon as the Unreported status is cleared by the alert reporting task, another block
alert may be reported without clearing the Active status, if the subcode has changed.
ALARM_SUM
The summary alarm is used for all process alarms in the block. The cause of the alert
is entered in the subcode field. The first alert to become active sets the Active status
in the Status parameter. As soon as the Unreported status is cleared by the alert
reporting task, another block alert may be reported without clearing the Active status,
if the subcode has changed.
ACK_OPTION
Used to set AUTO acknowledgment of alarms.
ALARM_HYS
The amount the alarm value must return within the alarm limit before the associated
active alarm condition clears.
HI_HI_PRI
The priority of the HI HI alarm.
HI_HI_LIM
The setting for the alarm limit used to detect the HI HI alarm condition.
HI_PRI
The priority of the HI alarm.
HI_LIM
The setting for the alarm limit used to detect the HI alarm condition.
LO_PRI
The priority of the LO alarm.
LO_LIM
The setting for the alarm limit used to detect the LO alarm condition.
LO_LO_PRI
The priority of the LO LO alarm.
LO_LO_LIM
The setting for the alarm limit used to detect the LO LO alarm condition.
HI_HI_ALM
The HI HI alarm data, which includes a value of the alarm, a timestamp of occurrence
and the state of the alarm.
HI_ALM
The HI alarm data, which includes a value of the alarm, a timestamp of occurrence
and the state of the alarm.
LO_ALM
The LO alarm data, which includes a value of the alarm, a timestamp of occurrence
and the state of the alarm.
LO_LO_ALM
The LO LO alarm data, which includes a value of the alarm, a timestamp of
occurrence and the state of the alarm.