Figure 21: Arithmetic Schematic Diagram - Honeywell SLG 700 Option Manual

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

3.12.1.
The range extension function has a graduated transfer controlled by two constants referenced to IN. An
internal value, g, is zero for IN less than RANGE_LO. It is one when IN is greater than RANGE_HI.
It is interpolated from zero to one over the range of RANGE_LO to RANGE_HI. The equation for
PV follows:
If the status of IN_LO is not usable and IN is usable and greater than RANGE_LO, then g is set to
one. If the status of IN is unusable, and IN_LO is usable and less than RANGE_HI, then g is set to
zero.
For three auxiliary inputs, six constants are used, and each input has a BIAS_IN_i and a GAIN_IN_i.
The output has a BIAS and a GAIN static constant. For the inputs, the bias is added, and the gain is
applied to the sum. The result is an internal value called t_i in the function equations. The equation for
each auxiliary input is the following:
If an auxiliary input is unstable, to assure smooth degradation, the flow compensation functions have
limits on the amount of compensation applied to the PV. The internal limited value is f.
Page 100

Figure 21: Arithmetic Schematic Diagram

Calculation of PV
���� = ��×���� + ( 1 − �� ) ×����_����
��_�� = (����_�� + ��������_����_��)��������_����_��
FOUNDATION Fieldbus Option User's Manual
Rev.5

Advertisement

Table of Contents
loading

Table of Contents