Block. Parameter
Unable to write
values to valid
device
parameters.
ATTENTION
Depending on the fieldbus interface application, device operating status and
parameter values may appear as text messages. The text in the table is
typical of values or messages seen when using the NI-FBUS configurator.
Critical Fault
In the case of a critical fault due to Memory Failure, NV/Static data loss or the
readback check failure, writes to the RESTART parameter twice, for the
transmitter to fully recover from the fault condition. Therefore:
1.
2.
3.
4.
Note that if a ROM error (Memory Failure) occurs in the resource block, it
may take up to 10 seconds for the fault to reappear.
Page 196
Value
Readback
Check Failed
(12)
Out-of-Service
(15)
Write "4" or "restart processor" to RESTART parameter of resource
block.
Wait until communication is established.
If the fault occurs again, repeat the write to the RESTART parameter.
If the fault occurs again, replace the transmitter communication module.
FOUNDATION Fieldbus Option User's Guide
Fault
Type
Critical
See Critical Fault NOTE.
Non-
Write proper mode to MODE_BLK
critical
parameter.
See "Resolving the block
Configur
ation
configuration errors".
Error
Action