Honeywell SLG 700 Option Manual page 29

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Block_ERR
Block Alarms
Bit
4
Local Override
5
Device Fault State Set
6
Device Needs
Maintenance Soon
7
Input Failure
8
Output Failure
9
Memory Failure
10
Lost Static data
11
Lost NV data
12
Readback Check failed
13
Device needs
maintenance now
14
Power-up
15
Out-of-Service
Rev.5
The block output is being set to track the value of the track
input parameter.
NOTE:
It is not supported by the transmitter.
If the Device Fault State condition is True.
NOTE:
It is not supported by the transmitter.
A diagnostic algorithm has found a warning condition. The NV
memory is approaching the maximum number of reliable
writes.
NOTE:
It is not supported by the transmitter.
When a sensor failure (open thermocouple) or sensor
conversion not accurate.
Output Failure detected by this block/back calculation input
has a status of Bad or Device Failure.
NOTE:
It is not supported by the transmitter.
A diagnostic algorithm has found a failure in memory (includes
all types) and the device is still able to communicate that
condition.
If the object's static data is Bad, then the object's database is
set to its default values.
The NV and static parameters are saved periodically. This
alarm occurs, if new data was supposed to be saved to NV at
the next NV write cycle, but prevented the write due to power
failure.
This indicates the readback of the actual continuous valve or
other actuator position in transducer units has failed.
A diagnostic algorithm has found an invalid condition, but the
device is still able to operate and communicate. The NV
memory has reached the maximum number of reliable writes.
NOTE:
It is not supported by the transmitter.
The resource is performing its first normal execution, after
power was applied to the device. It is not an error but
generates an alarm that says that normal operation was
interrupted and is now being restored.
NOTE:
It is not supported by the transmitter.
The actual mode is OOS. No control function blocks are being
processed.