Honeywell SLG 700 Option Manual page 68

Smartline level transmitter guided wave radar foundation fieldbus
Hide thumbs Also See for SLG 700:
Table of Contents

Advertisement

Parameter Name
TANK_HEIGHT
TANK_DIAMETER
VOLUME_OFFSET
STRAPPING_TABLE_DATE
VOLUME_STRAPPING_TABLE_SIZE
LEVEL_1
LEVEL_2
VOLUME_RD1
VOLUME_RD2
Page 52
FOUNDATION Fieldbus Option User's Manual
Description
Tank height is modifiable only when the tank shape
selected is vertical Bullet
Tank Diameter is modifiable only when the tank shape
selected is one among the below
1.
Sphere
2.
Horizontal Bullet
3.
Vertical Cylinder
4.
Horizontal Cylinder
5.
Vertical Bullet
The volume offset value to be added to all the volume
values for correction
Date of entry of Strapping Table can be updated
whenever the strapping table modification is done. The
format is MM/DD/YYYY HH:MM:SS
Strapping Table Size. Strapping table consists of Level_1
Table, Level_2 Table, Volume_RD1 Table and
Volume_RD2 table. Value of this limit the strapping table
entry. Strapping Table maximum size is 50.
Note: If the strapping table size is zero or strapping table
entry is invalid then device will not use strapping table
data.
This is the first half part of the Level Table which
supports entries for 25 elements. It can be updated when
Linearization Type is either in DRY or WET. While
executing Volume Wet Calculation Method, Level_1 table
cannot be edited by user. Product Level Value or
Interface level value (if Measured Product Type is Two
Liquid Flooded) is copied in the Level Table based on the
selected strapping table index. Level Table entry is
limited by the Volume strapping Table Size. If entry
exceeds Volume strapping table Size, the parameter
check error is thrown.
This is the second half part of the Level Table which
supports entries for 25 elements. It can be updated when
Linearization Type is either in DRY or WET. While
executing Volume Wet Calculation Method, Level_2 table
cannot be edited by user. Product Level Value or
Interface level value (if Measured Product Type is Two
Liquid Flooded) is copied in the Level Table based on the
selected strapping table index. Level Table entry is
limited by the Volume strapping Table Size. If entry
exceeds Volume strapping table Size, the parameter
check error is thrown.
This is the first half part of the volume Table which
supports entries for 25 elements. It can be updated when
the linearization type is either DRY or WET.
This is the second half part of the volume Table which
supports entries for 25 elements. It can be updated when
linearization type is either in DRY or WET.